2009-09-18 15:12:03 | ** FAILED REVIEW ** |
| |
| PLANS ARE NOT COMPLETE FOR REVIEW. THERE IS INFORMATION |
| NO YET SHOWN FOR MINIMUM CODE COMPLIANCE. THERE MAY |
| VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW ONCE |
| PLANS ARE COMPLETED. |
| |
| 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLANS |
| REVIEW AND NOT UNDER PERMIT APPLICATION. THIS IS BEING |
| NOTED AS THERE ARE CODE CHANGES COMING UP ON OCT 1ST, |
| 2009. |
| THIS WILL CHANGE TO THE 2008 NFPA-70 AND ALSO CHANGES |
| UNDER THE 2007 FBC. THERE WILL BE A SECOND ROUND OF |
| 2009 REVISIONS TO THE FBC. |
| |
| 2) NOTE: PLEASE SEE COMMENTS FROM ALL OTHER TRADES AS |
| THEY WILL GREATLY AFFECT THE SUBMISSION OF FUTURE |
| DOCUMENTS AND ELECTRICAL PLANS. EXAMPLES WOULD BE: |
| SEPARATE PERMITS FOR SEPARATE PROPERTIES, UNITY OF |
| TITLES, LIGHTING LEVELS PERMITTED. ETC |
| |
| 3) NOTE: PLEASE SUBMIT COMPLETE INFORMATION FOR |
| ELECTRICAL SYSTEM. PLEASE SUBMIT A COMPLETE ELECTRICAL |
| RISER DIAGRAM FOR SERVICE OR SERVICES WHICH WILL FEED |
| LIGHTING. BASED ON THE FACT THESE ARE TWO SEPARATE |
| LEGAL PROPERTIES, THERE MAY BE A NEED TO HAVE TWO |
| SEPARATE ELECTRICAL SERVICES. |
| PLEASE SEE NEC , 110.9,215.5,220,230,240,310 ETC GIVEN |
| AS GENERAL COMMENTS AS THERE IS NO INFORMATION ON PLANS |
| TO REVIEW FOR MINIMUM CODE COMPLIANCE. |
| |
| 4) NOTE: PLEASE BE SURE FIXTURE INFORMATION IS COMPLETE |
| ON PLANS. PLEASE BE SURE TO SEE 13-415.AB.2.2 FOR |
| ALLOWANCES OF UNCOVERED PARKING AREAS. |
| |
| 5) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR REQUIRED |
| OUTSIDE LIGHTING CONTROLS. MUST MEET MINIMUM CONTROLS |
| AS SET-FORTH IN SECTIONS GIVEN. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |