Plan Review Notes
Plan Review Notes For Permit 09080428
Permit Number 09080428
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-18 12:17:36 
  
 ** FAILED REVIEW **
  
 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A
 LICENSED CONTRACTOR.
  
 2) NOTE: THE SUBMITTED RISER AS SHOWN ON E5.1 CONTAINS
 A SUBSTANTIAL AMOUNT OF CODE VIOLATIONS. THE RISER
 SHOWN FOR FEEDS TO FIRE PUMP AND SEVERAL OTHER ASPECTS
 OF SERVICE AS SHOWN IN VIOLATION OF TOO MANY CODES TO
 NOTE. THE APPLIED SCOPE OF WORK IS FOR THE SECOND FLOOR
 TENANT. PLEASE ONLY INCLUDE ELECTRICAL FOR THIS
 RELEVANT SPACE AND EQUIPMENT ONLY.
 ** IT SHOULD BE NOTED IF THE ELECTRICAL AS SHOWN ON
 RISER IS THE ACTUAL INSTALLATION THERE SHOULD BE
 CONCERNS OVER THE INSTALLATION AS SHOWN.
 THERE ARE SEVERAL ITEMS SHOWN ON RISER WHICH ARE LIFE
 SAFETY AND FIRE HAZARDS CONCERNS. IF RISER IS ACCURATE
 THEN THESE ITEMS SHOULD BE ADDRESSED BY THE APPROPRIATE
 PARTIES RESPONSIBLE FOR THE BUILDING.
 PLEASE SEE NFPA-110, NFPA-20 AND NFPA-70 FOR LIFE
 SAFETY, LEGALLY REQUIRED SYSTEMS ALONG WITH FIRE PUMP
 INSTALLATION MINIMUMS.
  
 ** THIS WAS NOTED ON A PREVIOUS PLAN REVIEW SEVERAL
 YEARS AGO.
  
 2) NOTE: THE LOAD SHOWN ON PANEL 2MA APPEARS TO INCLUDE
 ONLY LOADS FOR PANELS 2LA, 2A AND 2B. WHERE IS THE LOAD
 FOR 1LA?
 ALL OF THESE PANELS ARE SHOWN FROM THE SAME 75KVA
 TRANSFORMER. THE TOTAL LOADS AS SHOWN ARE EXCEEDING THE
 RATING OF THE 75 KVA TRANSFORMER.
 PLEASE SEE 450 FOR MAXIMUM ALLOWABLE LOADS. PLEASE SEE
 NEC 220.12,220.14,220.42,220.44 ETC ALONG WITH
 215.3,230.42.
 LOAD CALCULATIONS SHOULD BE DONE TO ACCURATELY DEPICT
 ACTUAL LOAD ON SERVICE EQUIPMENT, TRANSFORMER.
 THE CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER
 ARE NOTED AS ONE RUN OF 250MCM. ALL PANELS AS SHOWN ARE
 100AMP MCB.
 THIS IS NOT POSSIBLE AS SHOWN/NOTED.
 PLEASE PROVIDE CONDUCTORS ON THE SECONDARY SIDE.
 240.4,240.21C, 310.16, 110.3, 110.14 ETC.
  
 3) NOTE: PANELS 2A AND 2B ARE SHOWN BEING FED FROM 2LA,
 HOWEVER NO BREAKERS ARE INDICATED IN PANEL SCHEDULE. IS
 PANEL 2LA A FEED-THRU LUG PANEL WITH DOUBLE TAPPED
 LUGS?
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  