Plan Review Notes
Plan Review Notes For Permit 09080427
Permit Number 09080427
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-18 11:24:35 
 ** FAILED REVIEW **
  
 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A
 LICENSED CONTRACTOR.
  
 2) NOTE: ROOM 1503 IS SHOWN AS A UTILITY/STORAGE ROOM.
 THE ELECTRICAL PANEL AND TRANSFORMER ARE NOT PERMITTED
 IN THIS LOCATION.
 240.24D.
 PLEASE KNOW THIS MAY ONLY BE A DEDICATED ELECTRICAL
 ROOM WITH SIGNAGE AS REQUIRED.
  
 2) NOTE: THE RISER ON SHEET E 5.1 IS NOT ACCURATE. THE
 PLANS INDICATE PANELS AND EQUIPMENT 15TH FLOOR YET THE
 RISER INDICATE THAT THERE IS A PANEL 16LA FED FROM THE
 SAME TRANSFORMER AS SHOWN FOR OTHER 15TH FLOOR PANELS.
 BASED ON THE EQUIPMENT ON E0.1 FOR THE ELECTRICAL ROOM
 THIS APPEARS IT SHOULD HAVE BEEN LABELED AS PANEL 15LA?
 THE TAPPED CONDUCTORS AS SHOWN ON TRANSFORMER SCHEDULE
 WOULD ALSO NOT BE ACCURATE.
 IF THIS EQUIPMENT DOES NOT APPLY TO THE SCOPE OF WORK
 OR TO THIS TENANT THEN IT MAY BE REMOVED FROM PLANS.
  
  
 ** AS THESE ARE THE ONLY COMMENTS, THEY COULD BE
 REDLINED ON AND FROM PLANS ONCE LICENSED CONTRACTOR IS
 ON APPLICATION. PLANS WILL BE REQUIRED TO BE REVISED AT
 SOME POINT TO ACCURATELY ADDRESS COMMENTS ABOVE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  