2009-09-18 11:24:35 | | | ** FAILED REVIEW ** | | | | 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A | | LICENSED CONTRACTOR. | | | | 2) NOTE: ROOM 1503 IS SHOWN AS A UTILITY/STORAGE ROOM. | | THE ELECTRICAL PANEL AND TRANSFORMER ARE NOT PERMITTED | | IN THIS LOCATION. | | 240.24D. | | PLEASE KNOW THIS MAY ONLY BE A DEDICATED ELECTRICAL | | ROOM WITH SIGNAGE AS REQUIRED. | | | | 2) NOTE: THE RISER ON SHEET E 5.1 IS NOT ACCURATE. THE | | PLANS INDICATE PANELS AND EQUIPMENT 15TH FLOOR YET THE | | RISER INDICATE THAT THERE IS A PANEL 16LA FED FROM THE | | SAME TRANSFORMER AS SHOWN FOR OTHER 15TH FLOOR PANELS. | | BASED ON THE EQUIPMENT ON E0.1 FOR THE ELECTRICAL ROOM | | THIS APPEARS IT SHOULD HAVE BEEN LABELED AS PANEL 15LA? | | THE TAPPED CONDUCTORS AS SHOWN ON TRANSFORMER SCHEDULE | | WOULD ALSO NOT BE ACCURATE. | | IF THIS EQUIPMENT DOES NOT APPLY TO THE SCOPE OF WORK | | OR TO THIS TENANT THEN IT MAY BE REMOVED FROM PLANS. | | | | | | ** AS THESE ARE THE ONLY COMMENTS, THEY COULD BE | | REDLINED ON AND FROM PLANS ONCE LICENSED CONTRACTOR IS | | ON APPLICATION. PLANS WILL BE REQUIRED TO BE REVISED AT | | SOME POINT TO ACCURATELY ADDRESS COMMENTS ABOVE. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|