Plan Review Notes
Plan Review Notes For Permit 09080425
Permit Number 09080425
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-18 10:34:32 
 ** FAILED REVIEW **
  
 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A
 LICENSED CONTRACTOR.
  
 2) NOTE: PLANS INDICATE TWO LIGHTING CIRCUITS. 16MA-27
 AND 16MA-29, HOWEVER PANEL SCHEDULE DOES NOT LIST
 CIRCUIT 27 FOR THIS TENANT. IT DOES LIST CIRCUIT #31,
 WHICH IS NOT ON THE PLANS.
 IF THIS HAD BEEN THE ONLY COMMENT PLANS WOULD HAVE BEEN
 REDLINED.
  
 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE
 16MA PANEL ON RISER. THIS IS THE 277/480V 225AMP PANEL
 WHICH IS SHOWN FEEDING TRANSFORMER AND OTHER PANELS.
 HOWEVER THE PANEL SCHEDULE FOR 16MA STATES THE SUB FEED
 TO THE SAME PANEL 16MA. ( MISPRINT?)
 PLEASE SEE THE RISER WHICH INDICATES TWO SECONDARY TAPS
 FROM THE 75KVA TRANSFORMER. ONE TAP TO 16LA AND ONE TO
 16LB. PER THE TRANSFORMER SCHEDULE THE SECONDARY
 CONDUCTORS ARE ONLY ONE SET OF 250MCM.
 THERE ARE TWO COMMENTS HERE.
 A) THERE IS ONLY ONE SET INDICATED, WHERE IS THE OTHER
 ONE?
 B) PANEL 16LA IS SHOWN AS A 100AMP MCB. 250 MCM WILL
 NOT FIT UNDER LUGS OF A 100AMP BREAKER. THIS IS
 BASICALLY THE SAME COMMENT FOR 16LB WHICH IS A 150AMP
 MCB PANEL WITH 250MCM.
  
 PLEASE MAKE ADJUSTMENTS AND CORRECTIONS.
 310.16,240.4,240.21C, 408.36 ETC SHOW TAPPED CONDUCTORS
 TO EACH.
  
 4) NOTE: PLEASE SEE KEY PLAN ON SHEET E-0.1. IN THE
 LOWER LEFT HAND SIDE IN THE STORAGE ROOM OF THIS NEW
 TENANT SPACE THERE APPEARS TO BE NEW PANELS. THERE ARE
 DARK SQUARE SHAPES WHICH APPEAR TO BE PANELS. BASED ON
 THE REST OF THE PLANS THERE ARE NO PANELS IN THE
 STORAGE ROOM. PLEASE SEE 110.26 AND 240.24D AS THESE
 WOULD NOT BE PERMITTED IN STORAGE CLOSETS.
  
 5) NOTE: PANEL 16LA AS SHOWN ON E0.1 DOES NOT MEET
 110.26 AS SHOWN. PLEASE VERIFY AND RELOCATE AS THIS IS
 A SAFETY CODE COMMENT.
  
 6) NOTE: THE AMOUNT OF FIXTURES INDICATED FOR THE
 CORRIDOR PERFORMANCE CALCULATIONS ARE SHORT BY A
 RECESSED LIGHTING FIXTURE. STATES 5 WHEN THERE ARE
 6.THIS WOULD NOT BE CONSIDERED A GROSS ERROR PER
 13-103.1
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  