2009-09-18 13:34:09 | ** FAILED REVIEW ** |
| |
| 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A |
| LICENSED CONTRACTOR. |
| |
| 2) NOTE: THE SUBMITTED RISER AS SHOWN ON E5.1 CONTAINS |
| A SUBSTANTIAL AMOUNT OF CODE VIOLATIONS. THE RISER |
| SHOWN FOR FEEDS TO FIRE PUMP AND SEVERAL OTHER ASPECTS |
| OF SERVICE AS SHOWN IN VIOLATION OF TOO MANY CODES TO |
| NOTE. THE APPLIED SCOPE OF WORK IS FOR THE SECOND FLOOR |
| TENANT. PLEASE ONLY INCLUDE ELECTRICAL FOR THIS |
| RELEVANT SPACE AND EQUIPMENT ONLY. |
| ** IT SHOULD BE NOTED IF THE ELECTRICAL AS SHOWN ON |
| RISER IS THE ACTUAL INSTALLATION THERE SHOULD BE |
| CONCERNS OVER THE INSTALLATION AS SHOWN. |
| THERE ARE SEVERAL ITEMS SHOWN ON RISER WHICH ARE LIFE |
| SAFETY AND FIRE HAZARDS CONCERNS. IF RISER IS ACCURATE |
| THEN THESE ITEMS SHOULD BE ADDRESSED BY THE APPROPRIATE |
| PARTIES RESPONSIBLE FOR THE BUILDING. |
| PLEASE SEE NFPA-110, NFPA-20 AND NFPA-70 FOR LIFE |
| SAFETY, LEGALLY REQUIRED SYSTEMS ALONG WITH FIRE PUMP |
| INSTALLATION MINIMUMS. |
| |
| ** THIS WAS NOTED ON A PREVIOUS PLAN REVIEW SEVERAL |
| YEARS AGO. |
| |
| 2) NOTE: THERE ARE INCONSISTENCIES WITH RISER ON PLANS |
| SUBMITTED FOR THIS SPACE AND PREVIOUSLY REVIEWED PLANS. |
| THE PLAN REVIEW ON SUITE #200 AND #202 HAD COMMENTS |
| WITH THE RESPECT TO LOADS ON PANEL 2MA. THIS WOULD |
| AFFECT THE LOAD SHOWN ON 1MA ON THIS PLANS. |
| THIS RISER IS COMPLETELY DIFFERENT. |
| |
| A) THERE ARE NO OTHER PANELS ON THE LOAD SIDE OF THE |
| TRANSFORMER FED FROM 2MA EXCEPT 2LA. |
| B) THE PANEL SCHEDULE FOR 1MA STATES IT HAS A FEED TO |
| PANEL 1XA, HOWEVER BASED ON THE RISER 1XA IS NOT EVEN |
| FED FROM 1MA. |
| C) PANEL 1MA DOES NOT LIST ANY OTHER PANELS SUCH AS |
| 2MA. IS THIS A FEED-THRU PANEL? |
| |
| PLEASE SEE 450 FOR MAXIMUM ALLOWABLE LOADS. PLEASE SEE |
| NEC 220.12,220.14,220.42,220.44 ETC ALONG WITH |
| 215.3,230.42. |
| LOAD CALCULATIONS SHOULD BE DONE TO ACCURATELY DEPICT |
| ACTUAL LOAD ON SERVICE EQUIPMENT, TRANSFORMER |
| PLEASE COORDINATE ALL EQUIPMENT FOR COMPLETED REVIEW. |
| PLEASE SHOW EQUIPMENT SPECIFIC TO SCOPE OF WORK AND ANY |
| EQUIPMENT WHICH IS BEING AFFECTED BY NEW WORK. |
| |
| 3) NOTE: PLEASE BE SURE ALL SHEETS ARE SIGNED THE SAME. |
| INITIALS ON SOME SHEETS? |
| FS 471.025 |
| |
| 4) NOTE: LIGHTING CIRCUITS FOR SUITE #103 NEED TO BE |
| SPECIFIC AND IDENTIFIED ON 1MA. ONLY STATES *LTS*. |
| PLEASE BE SURE THIS IS SPECIFIC AS REQUIRED BY REVISED |
| 408.4. |
| ** IF THIS WAS THE ONLY COMMENT OR ONE OF MINOR |
| COMMENTS IT WOULD HAVE BEEN REDLINED. |
| |
| 5) NOTE: PANEL 1LA IS SHOWN AS A THREE PHASE PANEL. |
| HOWEVER BASED ON THE PANEL SCHEDULE ITSELF, THIS IS |
| ALSO SHOWN AS A SINGLE PHASE PANEL. WHICH IS IT? |
| PLEASE COORDINATE SO THAT AN ACCURATE REVIEW OF CODE |
| REQUIRED CALCULATIONS CAN BE DONE. |
| 215.5, 230,240, 220. GIVEN AS GENERAL CHAPTERS AS THERE |
| ARE SEVERAL CODES WHICH WOULD APPLY. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |