 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE DESCRIPTION ON THE APPLICATION INDICATES
 ELECTRICAL WORK TO BE DONE UNDER THIS PERMIT BUT NO
 ELECTRICAL PLANS WERE SUBMITTED. SUBMIT PLANS
 INDICATING THE SCOPE OF WORK, OR REMOVE THE ELECTRICAL
 WORK FROM THE APPLICATION. 106.1 FBC AS AMENDED.
  
 2} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3).
 IF APPLICABLE.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  