Plan Review Notes For Permit 09080250
Permit Number 09080250
Review Stop M
Sequence Number 2
Notes
Date Text
2009-09-16 14:27:09PROVISO: 2007 RESIDENTIAL M1602.4
 TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCH (25 MM) UNDERCUT
 TO ACHIEVE PROPER RETURN AIR BALANCE.
  