Plan Review Notes
Plan Review Notes For Permit 09080250
Permit Number 09080250
Review Stop E
Sequence Number 2
Notes
Date Text
2009-09-16 15:04:07PROVISO:
 2007 FBC RESIDENTIAL R313.2.1
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED.
 EXCEPTIONS:
 INTERCONNECTION AND HARD-WIRING OF SMOKE ALARMS IN
 EXISTING AREAS SHALL NOT BE REQUIRED WHERE THE
 ALTERATIONS OR REPAIRS DO NOT RESULT IN THE REMOVAL OF
 INTERIOR WALL OR CEILING FINISHES EXPOSING THE
 STRUCTURE, UNLESS THERE IS AN ATTIC, CRAWL SPACE OR
 BASEMENT AVAILABLE WHICH COULD PROVIDE ACCESS FOR HARD
 WIRING AND INTERCONNECTION
  
  
 SMOKE ALARMS LOCATED WITHIN 20' OF COOKING WILL NEED TO
 BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE ALARMS AND
 SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20 FT)
 HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
  
 SERVICE OUTLETS FOR A/C EQUIPMENT.210.52(E), 210.8(3)
 OUTDOORS 210.63 .
  
 REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D), 21011.C.3
 210.8A1
  
  
  