2009-08-13 16:57:09RESIDENTIAL ELECTRICAL PLAN REVIEW
 PERMIT: 09080250
 ADD: 810 30TH ST
 CONT: JMA ELECTRIC/ 09080258
 TEL: (561)GLADES ROOFING CGC 954-593-5917
  
 1ST REVIEW
 ACTION: DENIED
 2005 NEC
  
 NOTE THE PERMIT APPLICATION INDICATES THAT THE
 ELECTRICAL UPGRADE TO "CODE"
  
 1A) PLANS FAIL TO IDENTIFY THE CODE CYCLE THAT THE
 PLANS ARE TO BE DESIGNED TO:
 2007 FBC/ 2009 SUPPLEMENTS
 2007 EXISTING BUILDING CODE/ 2009 SUPPLEMENTS
 2005 NEC
  
 1B) EXISTING BUILDING CODE: 401.4 A DESIGN PROFESSIONAL
 OR AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS
 OF ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE.
  
 2) PLEASE REVIEW THE ELECTRICAL PLANS VERSES THE
 MECHANICAL PLAN, THE UTILITY ROOM APPLIANCES AND A/C
 EQUIPMENT ARE LOCATED IN DIFFERENT LOCATION, PLEASE
 CORRELATE PLANS TO THE SAME LOCATION FOR ALL TRADES.
 106.1.2.
  
 3) SHEET 1 ALSO NEEDS TO CORRELATE THE PANEL SCHEDULE
 AND FLOOR PLAN TO REFLECT THE SAME CIRCUITRY IN THE
 PANEL SCHEDULEAS FLOOR PLAN. EXAMPLES ARE THE FLOOR
 PLAN INDICATES THE A/C CONDENSORS ON CIRCUIT 24-26WHERE
 AS THE PANEL SCHEDULE INDICATE 24-25. A/C HANDLER ON
 THE FLOOR PLAN ON CIRCUITS 2&4 IN PANEL SCHEDULE 2 IS
 GENERAL LIGHTING AND 4 IS RECEPTACLES.
 THERE ARE MORE THAN THESE DISCREPANCIES PLEASE REVIEW
 AND CORRECT. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
 106.1.1.
  
 4) THE AIR COMPRESSORS ELECTRICAL SYSMBOL IS ACTUALLY
 DRAWN IN AS A 240 OULET NOT AS A REQUIRED DISCONNECT
 PLEASE CORRECT.
 440.11 GENERAL. THE PROVISIONS OF PART II ARE INTENDED
 TO REQUIRE DISCONNECTING MEANS CAPABLE OF DISCONNECTING
 AIRCONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING
 MOTORCOMPRESSORS AND CONTROLLERS FROM THE CIRCUIT
 CONDUCTORS. PLEASE INDICATE A TRUE DISCONNECT.
  
 5) FLOOR PLAN INDICATES (2) SUB-PANELS LABELED "B"
 WHERE AS THE RISER DIAGRAM ONLY INDICATES A SINGLE
 PANEL, AGAIN PLEASE IDENTIFY WHICH PANEL IS WHERE,
 PANEL A AND PANEL B.
  
 6) THE OTHER ISSUE IS THE NEW 200 AMP DISCONNECT
 BREAKER, IS MISSING THE A/C RATING. 110.9 INTERRUPTING
 RATING. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING
 SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND THE
 CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE
 EQUIPMENT. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 OTHER THAN
 FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING AT
 NOMINAL CIRCUIT VOLTAGE SUFFICIENT FOR THE CURRENT THAT
 MUST BE INTERRUPTED .
  
 7A) FLOOR PLAN ALSO INDICATES THE UTILITY ROOM PANEL
 JUST THE WIDTH OF THE PANEL PLEASE REVIEW: 408.4
 CIRCUIT DICTIONARY. ALL CIRCUITS AND CIRCUIT
 MODIFICATINS SHALL BE LEGIBLY IDENTIFIED AS TO PURPOSE
 OR USE ON A CIRCUIT DIRECTORY LOCATED ON THE FACE OR
 INSIDE OF THE PANEL DOOR IN THE CASE OF A PANEL OARD,
 AND AT EACH SWITCH ON A SWITCHBOARD. NOTE IDENTIFY
 CIRCUITS BY ROOM NOT GENERAL LIGHTING OR RECEPTACLES.
  
 7B) PANEL LOCATIONS NEED TO COMPLY WITH: 110.26 (1)
 DEPTH OF WORKING SPACE, (2) WIDTH OF WORKING SPACE &
 (3) HEIGTH OF WORKING SPACE. FOR BOTH PANEL LOCATIONS.
 THE DEDICATED ELECTRICAL SPACE MUST BE CLEAR OF ANY
 PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR EQUIPMENT
 FOREIGN TO THE ELECTRICAL INSTALLATION. PLUMBING,
 HEATING, VENTILATION, AND
 AIR-CONDITIONING PIPING, DUCTS, AND EQUIPMENT MUST BE
 INSTALLED OUTSIDE THE WIDTH AND DEPTH ZONE.
  
 8) NOTE THE PANEL SCHEDULE DOES NOT INCLUDE THE RANGE,
 WATER HEATER NOR DRYER SYMBOL INDICATING ELECTRICAL
 CONNECTIONS, IT IS UNKNOWN IF THESE APPLIANCES ARE
 ELECTRIC OR GAS, IF GAS THE SMOKE ALARMS WILL ALSO NEED
 TO BE CARBON MONOXIDE DETECTORS ALSOFL S S 553.885.
  
 9) THE BACK REAR BEDROOM DOES INDICATE A SMOKE ALARM
 WITHIN THE UNIT BUT NOT ONE OUTSIDE OF THE BEDROOM THIS
 ALSO HOLDS TRUE FOR THE MASTER BEDROOM FBC RESIDENTIAL
 313.2(2) AND NFPA 72.
  
 10) THE SMOKE ALARMS LOCATED WWITHIN 20' OF COOKING
 WILL NEED TO BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE
 ALARMS AND SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20
 FT) HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
  
 11) UTILITY ROOM CIRCUIT IS NOT SHOWN ON PLANS
 REQUIRING A GFCI CIRCUIT. 210.8(C)(2) LAUNDRY BRANCH
 CIRCUIT.
  
 12) BEDROOMS MISSING OUTLETS ON PLANS, PLEASE PROVIDE
 ARC FAULT OUTLET CIRCUIT PER 210.12(B) DWELLING UNIT
 BEDROOMS.210.52OUTLET SPACING.
  
 13)LIGHTING NOT SHOWN ON PLANS SWITCH LOCATIONS
 210.70.INTERIOR LOCATIONS
  
 14) EXTERIOR EXIT LIGHTS NOT SHOWN NOR SWITCH LOCATIONS
 210.70.
  
 15) REQUIRED SERVICE OUTLETS FOR A/C
 EQUIPMENT.210.52(E), 210.8(3) OUTDOORS 210.63 .
  
 16) THERMOSTATS ARE NOT SHOWN.
  
 17) 2ND AIR HANDLIER NOT SHOWN ON PANEL SCHEDULE.
  
 18) THE ELECTRIC RISER IS MISSING GROUND ROD LENGTH,
 250.66 & TABLE 250.66.
  
 19) LAUNDRY/ WASHER PLEASE REVIEW 210.52, 210.11C2 &
 220.52.3
  
 20) MISSING EQUIPMENT GROUND BETWEEN MAIN AND PANEL
 250.122
  
 21) REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D),
 21011.C.3 210.8A1
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved