Plan Review Notes
Plan Review Notes For Permit 09080245
Permit Number 09080245
Review Stop M
Sequence Number 2
Notes
Date Text
2009-09-30 10:17:51MECHANICAL PROVISO:
 M1602.4 BALANCED RETURN AIR. RESTRICTED RETURN AIR
 OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL
 ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE
 RETURN GRILL OR WHEN CEILING SPACES ARE USED AS RETURN
 PLENUMS AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE
 PORTION OF THE RETURN PLENUM TO ANOTHER. PROVISIONS
 SHALL BE MADE IN RESIDENTIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR.
 TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (4.6 MM)
 (OF GRILLE AREA) TO 100 CFM (0.05 M3/S) (OF SUPPLY AIR)
 FOR SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING
 AN UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO
 ACHIEVE PROPER RETURN AIR BALANCE.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 SFP-100
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved