2009-08-18 09:47:43RESIDENTIAL MECHANICAL PLAN REVIEW
 PERMIT: 09080245
 ADD: 822 30TH ST
 CONT: GLADES ROOFING
 TEL: (561)GLADES ROOFING CGC 954-593-5917
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) SHEET 2OF 2 INDICATES PLENUM RRETURNS ABOVE THE
 CEILING WITH A R-30 VALUE FOR INSULATION. IF THE AIR
 HANDLIERS ARE AS SHOWN AS A VERTICAL UNIT WITH THE
 RETURN AIR BEING LOCATED AT THE BOTTOM OF THE UNIT WHY
 DOES THE PLAN CALL FOR A PLENUN RETURN LOCATED WITHIN
 THE ATTIC? M1601.9 CAVITIES OF THE BUILDING
 STRUCTURE.EXCEPTION: SURFACES BETWEEN THE PLENUM AND
 CONDITIONED SPACES FROM WHICH THE RETURN/MIXED AIR IS
 DRAWN.
 BUILDING CAVITIES BENEATH A ROOF DECK THAT WILL BE USED
 AS RETURN AIR PLENUMS SHALL HAVE AN INSULATED ROOF WITH
 THE INSULATION HAVING AN R-VALUE OF AT LEAST R-19.
  
 3) RETURN AIR TRANSFER DUCTS & GRILLS;
 3A) PLANS INDICATE BEDROOMS 2 & 3 ALL HAVING FLEX
 RETURN TRANSFER DUCTS SIZE NOT PROVIDED AND EACH HAVING
 A 8X8 INCH RETURN AIR GRILL TRANSFERING INTO A SINGLE
 RETURN WITH A SINGLE 8X8 INCH TRANSFER GRILLE. PLEASE
 SHOW COMPLIANCE WITH :
 M1602.4 TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING
 THE RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCH (25 MM) UNDERCUT
 TO ACHIEVE PROPER RETURN AIR BALANCE.
  
 3B) SHEET 2 OF 2 INDICATES THE AIR HANDLER LOCATED IN A
 CLOSET WITH A RETURN AIR GRILLE LOCATED IN THE DOOR,
 PLEASE PROVIDE SIZE OF RETURN AIR GRILLE. M1602.4
 BALANCED RETURN AIR. RESTRICTED RETURN AIR OCCURS IN
 BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL ZONES AND
 CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE RETURN
 GRILL OR WHEN CEILING SPACES ARE USED AS RETURN PLENUMS
 AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE PORTION
 OF THE RETURN PLENUM TO ANOTHER. PROVISIONS SHALL BE
 MADE IN RESIDENTIAL BUILDINGS TO AVOID UNBALANCED AIR
 FLOWS AND PRESSURE DIFFERENTIALS CAUSED BY RESTRICTED
 RETURN AIR.
 TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (4.6 MM)
 (OF GRILLE AREA) TO 100 CFM (0.05 M3/S) (OF SUPPLY AIR)
 FOR SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING
 AN UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO
 ACHIEVE PROPER RETURN AIR BALANCE.
  
 4) PLEASE LOOK AT RETURN AIR GRILLE LOCATON AND THE
 MANUFACTURERS SPECS FOR TTHTE SMOKE ALARMS AS TO THE
 CLOSENESS OF RETURN AIR GRILLES AND ALSO BATHROOM
 LOCATIONS!
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved