Plan Review Notes
Plan Review Notes For Permit 09080245
Permit Number 09080245
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-18 09:30:59RESIDENTIAL ELECTRICAL PLAN REVIEW
 PERMIT: 09080245
 ADD: 822 30TH ST
 CONT: GLADES ROOFING
 TEL: (561)GLADES ROOFING CGC 954-593-5917
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) THE PERMIT APPLICATION UNDER DESCRIPTION OF WORK
 DOES NOT PROVIDE WHAT ELECTRICAL UPGRADES ARE GOING TO
 TAKE PLACE UNDER THIS PERMIT, PLEASE PROVIDE AN
 ITEMIZED LIST OF WHAT ELECTRICAL UPGRADES ARE TO OCCUR,
 THE ELECTRICAL LIST FROM 09080250 WOULD BE MUCH THE
 SAME FOR THIS PERMIT BUT NOT KNOWING WHAT WILL BE
 COVERED MAKES THE REVIEW SOMEWHAT MEANINGLESS. THESE
 COMMEENTS WILL BE GENERALLITIES UNTIL THE EXTENT OF
 WORK IS KNOWN.
  
 106.1.1 ADMINISTRATIVE CODE, CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3) DISCREPANCY IN ELECTRICAL PANEL, CIRCUITS 12-13 ARE
 DESINATED FOR A/C COMPRESSOR WHEREAS THE PLANS INDICATE
 CIRCUITS 16& 18.
  
 4) THE AIR COMPRESSORS ELECTRICAL SYSMBOL IS ACTUALLY
 DRAWN IN AS A 240 OULET NOT AS A REQUIRED DISCONNECT
 PLEASE CORRECT.
 440.11 GENERAL. THE PROVISIONS OF PART II ARE INTENDED
 TO REQUIRE DISCONNECTING MEANS CAPABLE OF DISCONNECTING
 AIRCONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING
 MOTORCOMPRESSORS AND CONTROLLERS FROM THE CIRCUIT
 CONDUCTORS. PLEASE INDICATE A TRUE DISCONNECT.
  
 5) FLOOR PLAN INDICATES A JUNCTION BOX IN THE KITCHEN,
 IS THIS TRUELY A JUNCTION BOX OR THE PANEL, IF A
 JUNCTION BOX WHERE IS THE PANEL?
  
 6) THE OTHER ISSUE IS THE NEW 200 AMP DISCONNECT
 BREAKER, IS MISSING THE A/C RATING. 110.9 INTERRUPTING
 RATING. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING
 SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND THE
 CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE
 EQUIPMENT. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 OTHER THAN
 FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING AT
 NOMINAL CIRCUIT VOLTAGE SUFFICIENT FOR THE CURRENT THAT
 MUST BE INTERRUPTED .
  
 7A) PANEL SCHEDULE REQUIRED PLEASE REVIEW: 408.4
 CIRCUIT DICTIONARY. ALL CIRCUITS AND CIRCUIT
 MODIFICATINS SHALL BE LEGIBLY IDENTIFIED AS TO PURPOSE
 OR USE ON A CIRCUIT DIRECTORY LOCATED ON THE FACE OR
 INSIDE OF THE PANEL DOOR IN THE CASE OF A PANEL OARD,
 AND AT EACH SWITCH ON A SWITCHBOARD. NOTE IDENTIFY
 CIRCUITS BY ROOM NOT GENERAL LIGHTING OR RECEPTACLES.
  
 7B) PANEL LOCATIONS NEED TO COMPLY WITH: 110.26 (1)
 DEPTH OF WORKING SPACE, (2) WIDTH OF WORKING SPACE &
 (3) HEIGTH OF WORKING SPACE. FOR BOTH PANEL LOCATIONS.
 THE DEDICATED ELECTRICAL SPACE MUST BE CLEAR OF ANY
 PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR EQUIPMENT
 FOREIGN TO THE ELECTRICAL INSTALLATION. PLUMBING,
 HEATING, VENTILATION, AND
 AIR-CONDITIONING PIPING, DUCTS, AND EQUIPMENT MUST BE
 INSTALLED OUTSIDE THE WIDTH AND DEPTH ZONE.
  
 8) NOTE THE PANEL SCHEDULE DOES NOT INCLUDE THE RANGE(
 GAS), NOR DRYER SYMBOL INDICATING ELECTRICAL
 CONNECTIONS, IT IS UNKNOWN IF THESE APPLIANCES ARE
 ELECTRIC OR GAS, GAS RANGE WILL REQUIRE THE SMOKE
 ALARMS WILL NEED TO BE CARBON MONOXIDE DETECTORS ALSOFL
 S S 553.885.
  
 9) THE BEDROOMS DO NOT INDICATE A SMOKE ALARM WITHIN
 THE UNIT NOR OUTSIDE OF THE BEDROOM PLEASE REVIEW FBC
 RESIDENTIAL 313.2(2) AND NFPA 72.
  
 10) THE SMOKE ALARMS LOCATED WWITHIN 20' OF COOKING
 WILL NEED TO BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE
 ALARMS AND SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20
 FT) HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
  
 11) UTILITY ROOM CIRCUIT IS NOT SHOWN ON PLANS
 REQUIRING A GFCI CIRCUIT. 210.8(C)(2) LAUNDRY BRANCH
 CIRCUIT.
  
 12) BEDROOMS MISSING OUTLETS ON PLANS, PLEASE PROVIDE
 ARC FAULT OUTLET CIRCUIT PER 210.12(B) DWELLING UNIT
 BEDROOMS.210.52OUTLET SPACING.
  
 13)LIGHTING NOT SHOWN ON PLANS SWITCH LOCATIONS
 210.70.INTERIOR LOCATIONS
  
 14) EXTERIOR EXIT LIGHTS NOT SHOWN NOR SWITCH LOCATIONS
 210.70.
  
 15) REQUIRED SERVICE OUTLETS FOR A/C
 EQUIPMENT.210.52(E), 210.8(3) OUTDOORS 210.63 .
  
 16) THERMOSTATS ARE NOT SHOWN.
  
 17) THE ELECTRIC RISER IS MISSING GROUND ROD LENGTH,
 250.66 & TABLE 250.66.
  
 18) LAUNDRY/ WASHER PLEASE REVIEW 210.52, 210.11C2 &
 220.52.3
  
 19) MISSING EQUIPMENT GROUND BETWEEN MAIN AND PANEL
 250.122
  
 20) REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D),
 21011.C.3 210.8A1
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  