2009-08-17 16:38:22 | RESIDENTIAL BUILDING PLAN REVIEW |
| PERMIT: 09080245 |
| ADD: 822 30TH ST |
| CONT: GLADES ROOFING |
| TEL: (561)GLADES ROOFING CGC 954-593-5917 |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| BUILDING WITH 2009 SUPPLEMENTS. |
| |
| PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS |
| PERMIT. |
| 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 403, 404 AND 405 OF THIS CODE. |
| |
| 2) PLANS DO NOT INDICATE ANY WIND DESIGN DRITERIA: |
| |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| |
| 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| 3) NEITHER THE PLANS NOR NOA INDICATE IF THESE WINDOWS |
| ARE TO BE FASTEND THROUGH WOOD BUCKS, THE NOA SUBMITTED |
| IS FOR FLANGED TYPE INSTALATION, THE CONCERN IS THE |
| REQUIRED SEPERATION FROM GLASS TO SHUTTER IS 2 5/8 TO 3 |
| 5/8 INCHES PLEASE INDICATE CODE COMPLIANCE FOR BOTH |
| ISSUES. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 4) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE SQ. FT |
| OF ROOF REPAIR AND WHAT PERCENTAGE.EXISTING BUILDING |
| CODE. 611.1.1 NOT MORE THAN 25 PERCENT OF THE TOTAL |
| ROOF AREA OR ROOF SECTION OF ANY EXISTING BUILDING OR |
| STRUCTURE SHALL BE REPAIRED, REPLACED OR RECOVERED IN |
| ANY 12 MONTH PERIOD UNLESS THE ENTIRE ROOFING SYSTEM OR |
| ROOF SECTION CONFORMS TO REQUIREMENTS OF THIS CODE. |
| |
| STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| NOTICE. |
| |
| OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| - 5:00 PM. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| SURVEY: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |