2009-08-11 13:17:53RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 FLAT ROOF COMMENTS:
  
 1- FLAT ROOF NOA 09-0224.01 SUBMITTED IS MISSING THE
 APPROVED ASSEMBLY TO BE INSTALLED. PROVIDE PAGE SHOWING
 SELECTED APPROVED ASSEMBLY. TO VERIFY DESIGN PRESSURES
 OF SEC. R301.
  
 2- CLEARLY IDENTIFY WHICH BASE SHEET FASTENING OPTION
 IS GOING TO BE INSTALLED. TO VERIFY DESIGN PRESSURES OF
 SEC. R301.
  
 3: GENERAL LIMITATION #7 OF NOA SUBMITTED REQUIRES RAS
 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS TO BE DONE BY A DESIGN PROFESSIONAL. RAS
 117 CALCULATIONS NEED TO BE SIGNED AND SEALED. SEE
 GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 ***NOTES: A) DESIGN PROFESSIONAL TO TAKE INTO
 CONSIDERATION THAT ACCORDING TO 2009 REVISIONS TO THE
 FBC 2007 THIS BUILDING IS LOCATED ON EXPOSURE "C".
 B) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT MAY NOT BE GOOD FOR THIS
 BUILDING BECAUSE THE DESIGN PRESSURES OF THE ASSEMBLY
 DON'T MEET THE DESIGN PRESSURES FOR THIS BUILDING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER