Plan Review Notes For Permit 09080243 |
Permit Number |
09080243 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-08-11 13:17:53 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | FLAT ROOF COMMENTS: | | | | 1- FLAT ROOF NOA 09-0224.01 SUBMITTED IS MISSING THE | | APPROVED ASSEMBLY TO BE INSTALLED. PROVIDE PAGE SHOWING | | SELECTED APPROVED ASSEMBLY. TO VERIFY DESIGN PRESSURES | | OF SEC. R301. | | | | 2- CLEARLY IDENTIFY WHICH BASE SHEET FASTENING OPTION | | IS GOING TO BE INSTALLED. TO VERIFY DESIGN PRESSURES OF | | SEC. R301. | | | | 3: GENERAL LIMITATION #7 OF NOA SUBMITTED REQUIRES RAS | | 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND | | CORNER AREAS TO BE DONE BY A DESIGN PROFESSIONAL. RAS | | 117 CALCULATIONS NEED TO BE SIGNED AND SEALED. SEE | | GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | | | ***NOTES: A) DESIGN PROFESSIONAL TO TAKE INTO | | CONSIDERATION THAT ACCORDING TO 2009 REVISIONS TO THE | | FBC 2007 THIS BUILDING IS LOCATED ON EXPOSURE "C". | | B) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #9, THEN IT MAY NOT BE GOOD FOR THIS | | BUILDING BECAUSE THE DESIGN PRESSURES OF THE ASSEMBLY | | DON'T MEET THE DESIGN PRESSURES FOR THIS BUILDING. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|