2009-08-20 14:35:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 REFERENCE SHEET E1:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} 13-415.AB.2.2 EXTERIOR BUILDING LIGHTING POWER. THE
 TOTAL EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL
 EXTERIOR BUILDING APPLICATIONS IS THE SUM OF THE
 INDIVIDUAL LIGHTING POWER DENSITIES PERMITTED IN TABLE
 13-415.AB.2.2 FOR THESE APPLICATIONS PLUS AN ADDITIONAL
 UNRESTRICTED ALLOWANCE OF 5% OF THAT SUM. TRADE-OFFS
 ARE ALLOWED ONLY AMONG EXTERIOR LIGHTING APPLICATIONS
 LISTED IN THE TABLE 13-415.AB.2.2, "TRADABLE SURFACES"
 SECTION. EXTERIOR LIGHTING FOR ALL APPLICATIONS (EXCEPT
 THOSE INCLUDED IN THE EXCEPTIONS TO SECTION 13-415.0
 AND THIS SECTION) SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 13-415.AB.2.1.*** COMPLY WITH SAME.THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS. SUBMIT A LEGEND OF FIXTURE TYPES AND
 WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 NOTE: LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR
  
 3} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 THE LUMINAIRES BEING INSTALLED.106.3.5.2 FBC AS
 AMENDED.
  
 4} NOTE: SEE NFPA-101 FOR EGRESS LIGHTING REQUIREMENTS,
 DEMONSRARE COMPLIANCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  
  
  
  