Date |
Text |
2009-08-20 14:35:34 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 |
| NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| REFERENCE SHEET E1: |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| FS, RESPECTIVELY. |
| THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| IF EXEMPTIONS APPLY. |
| |
| 2} 13-415.AB.2.2 EXTERIOR BUILDING LIGHTING POWER. THE |
| TOTAL EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL |
| EXTERIOR BUILDING APPLICATIONS IS THE SUM OF THE |
| INDIVIDUAL LIGHTING POWER DENSITIES PERMITTED IN TABLE |
| 13-415.AB.2.2 FOR THESE APPLICATIONS PLUS AN ADDITIONAL |
| UNRESTRICTED ALLOWANCE OF 5% OF THAT SUM. TRADE-OFFS |
| ARE ALLOWED ONLY AMONG EXTERIOR LIGHTING APPLICATIONS |
| LISTED IN THE TABLE 13-415.AB.2.2, "TRADABLE SURFACES" |
| SECTION. EXTERIOR LIGHTING FOR ALL APPLICATIONS (EXCEPT |
| THOSE INCLUDED IN THE EXCEPTIONS TO SECTION 13-415.0 |
| AND THIS SECTION) SHALL COMPLY WITH THE REQUIREMENTS OF |
| SECTION 13-415.AB.2.1.*** COMPLY WITH SAME.THIS CAN BE |
| DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE |
| SCHEDULE TO CORRELATE WITH THE ONES IN THE |
| CALCULATIONS. SUBMIT A LEGEND OF FIXTURE TYPES AND |
| WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE |
| CALCULATIONS. |
| |
| NOTE: LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION |
| SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| PHOTOSENSOR |
| |
| 3} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| THE LUMINAIRES BEING INSTALLED.106.3.5.2 FBC AS |
| AMENDED. |
| |
| 4} NOTE: SEE NFPA-101 FOR EGRESS LIGHTING REQUIREMENTS, |
| DEMONSRARE COMPLIANCE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |
| |
| |
| |
| |
| |
| |
| |