2009-08-27 13:12:586501 NORTH JOG ROAD
 PERMIT NUMBER 09080231
  
 1. WRONG LIFE SAFETY CODE REFERENCED ON COVER SHEET.
 SHOULD READ NFPA 101, 2006 EDITION.
  
 2. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRIC CODE.
  
 3. PLEASE ILLUSTRATE ALL ILLUMINATED EXIT SIGNS,
 EMERGENCY LIGHTS, FIRE ALARM EQUIPMENT AND EXIT DOORS.
  
 4. PLEASE INDICATE FIRE SEPARATION BETWEEN MAINTENANCE
 SHOP AND GENERAL OFFICE AREA.
  
 5. PLEASE INDICATE THE LOCATION OF ANY FIRE DOORS.
  
 6. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 REPLACED CEILING AREA.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM REMODEL.
  
 8. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER REMODEL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX