2009-08-24 14:00:50 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 |
| NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE |
| INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A |
| SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD |
| DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR |
| LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING |
| FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN |
| USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING |
| POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| SECTION13-415.B.1THIS CAN BE DEMONSTRATED ON THE PLANS |
| INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN FOR |
| THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. |
| INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE |
| WITH THE ONES IN THE CALCULATIONS. |
| |
| 2} 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED BY |
| CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE |
| CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL |
| LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE |
| READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE |
| THE CONTROLLED LIGHTING. A. A CONTROL DEVICE SHALL BE |
| INSTALLED THAT AUTOMATICALLY TURNS LIGHTING OFF WITHIN |
| 30 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, EXCEPT |
| SPACES WITH MULTI-SCENE CONTROL, IN THE FOLLOWING: |
| 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS, |
| LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE |
| CLASSROOMS) |
| 2. CONFERENCE/MEETING ROOMS. |
| 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |