2009-08-19 14:40:55BUILDING PLAN REVIEW
 PERMIT: 09080231
 ADD: 6501 N JOG RD
 CONT: ANDREA CONSTRUCTION
 TEL: (561)358-4797
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 AND RULES AND REGULATIONS AS DETERMINED BY THE BUILDING
 OFFICIAL. SHEET A-001 & A-002 INDICATE A MAINTENANCE
 SHOP FIRST FLOOR AND WHAT APPEARS TO BE A MEZZANINE
 LEVEL ABOVE. THE PLANS DO NOT INDICATE THE SQUARE
 FOOTAGE OF THE ROOM ( FIRST FLOOR) TO DETERMINE IF THIS
 AREA IS A TRUE MEZZANINE, PLEASE REVIEW SECTION 505.2
 AREA LIMITATIONS ON MEZZANINES.
  
 3) THE SECOND ISSUE WHICH CAN NOT BE ANSWERED AT THIS
 TIME IS THE OPENNESS REQUIREMENTS (505.4) FOR MEZZANNE
 IT APPEARS EXCEPTION# 1MAY APPLY BUT WITH NOT KNOWING
 THE FLOOR AREA BELOW AND IF TTHE EXISTING OFFICE AND
 CONFERENCE ROOM ARE CONSIDERED PART OF TTHE ENCLOSED
 MEZZANINE THE OCCUPANT LOAD MAY THEN RISE ABOVE 10.
  
 4A) WITH ONLY SHOWING A PORTION OF THE BUILDING THE
 NEXT ISSUE IT APPEARS THIS BUILDING IS TO BE CONSIDERED
 A MIXED OCCUPANCY OR DOES THE MAINTENCE SHOP MEET THE
 REQUIREMENT 508.3.1 ACCESSORY OCCUPANCIES BETWEEN THE
 MAINTENANCE SHOP AND THE BUSINESS OCCUPANCY. IF NOT
 PLEASE PROVIDE OCCUPANCY SEPERATION AND OPENING
 PROTECTIVES.
 TABLE 508.3.3 AND 715 OPENING PROTECTIVES.
  
 4B) IF OCCUPANCY SEPERATION IS DETERMINED TO BE NEEDED
 PLEASE SEE REVIEW CUT SECTIONS OF WALLS THAT WILL NEED
 TO EXTEND TO THE DECK ABOVE TO OBTAIN A IFE RATING.
 708.4 CONTINUITY.
  
  
 5) SHEET A.003 WALL SECTION DETAILS ALSO INDICATES THE
 R-30 BATT INSULATION LAYING ON TOP OF THE DROP IN
 CEILING PANELS. 13-404.AB.1 ROOF INSULATION SHALL NOT
 BE INSTALLED ON A SUSPENDED CEILINGWITH REMOVABLE
 PANELS.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved