Date |
Text |
2009-08-14 14:53:01 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| FBC-2007 CHAPTER 11 |
| |
| 1. THE ADDRESS ON THE APPLICATION IS INDICATED AS 100 S |
| DIXIE HWY, BUT THE TITLE BLOCK OF EACH SHEET INDICATES |
| THE ADDRESS AS 340 DIXIE HWY. PLEASE CORRELATE THE |
| ADDRESS IN THE TITLE BLOCKS WITH THE ADDRESS OF RECORD |
| FOR THE PCN NUMBER. SECTION 106.1.1. |
| |
| 2. INDICATE THE USE OF THE ROOM WITH THE SINK |
| INSTALLED. SECTION 106.1.2, (MORE INFORMATION |
| REQUIRED). IF SINK IS REQUIRED TO BE ACCESSIBLE, THEN |
| SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| WITH ALL SUBSECTIONS. |
| |
| 3. A DRINKING FOUNTAIN IS REQUIRED. TABLE 403.1. SHOW |
| THE LOCATION OF THE REQUIRED DRINKING FOUNTAIN. |
| |
| 4. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| WELL AS SECTION 11-4.1.3(10(A) PROVISIONS FOR THOSE WHO |
| HAVE DIFFICULITY BENDING OR STOOPING. |
| |
| 5. SHT3.0M SANITARY RISER DIAGRAM. A CHECK VALVE AND A |
| FULL OPEN VALVE ON THE DISCHARGE SIDE OF THE CHECK |
| VALVE SHALL BE INSTALLED IN THE PUMP OR EJECTOR |
| DISCHARGE PIPING BETWEEN THE PUMP OR EJECTOR AND THE |
| GRAVITY DRAINAGE SYSTEM. SECTION 712.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |