Plan Review Notes
Plan Review Notes For Permit 09080218
Permit Number 09080218
Review Stop P
Sequence Number 1
Notes
Date Text
2009-08-14 14:53:01DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. THE ADDRESS ON THE APPLICATION IS INDICATED AS 100 S
 DIXIE HWY, BUT THE TITLE BLOCK OF EACH SHEET INDICATES
 THE ADDRESS AS 340 DIXIE HWY. PLEASE CORRELATE THE
 ADDRESS IN THE TITLE BLOCKS WITH THE ADDRESS OF RECORD
 FOR THE PCN NUMBER. SECTION 106.1.1.
  
 2. INDICATE THE USE OF THE ROOM WITH THE SINK
 INSTALLED. SECTION 106.1.2, (MORE INFORMATION
 REQUIRED). IF SINK IS REQUIRED TO BE ACCESSIBLE, THEN
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24
 WITH ALL SUBSECTIONS.
  
 3. A DRINKING FOUNTAIN IS REQUIRED. TABLE 403.1. SHOW
 THE LOCATION OF THE REQUIRED DRINKING FOUNTAIN.
  
 4. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULITY BENDING OR STOOPING.
  
 5. SHT3.0M SANITARY RISER DIAGRAM. A CHECK VALVE AND A
 FULL OPEN VALVE ON THE DISCHARGE SIDE OF THE CHECK
 VALVE SHALL BE INSTALLED IN THE PUMP OR EJECTOR
 DISCHARGE PIPING BETWEEN THE PUMP OR EJECTOR AND THE
 GRAVITY DRAINAGE SYSTEM. SECTION 712.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved