Plan Review Notes
Plan Review Notes For Permit 09080218
Permit Number 09080218
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-08-20 11:50:16*****DENIED*****
  
 1. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2. ON THE COVER SHEET (C1), THE DRAWING INDEX INDICATES
 THAT SHEET 1.1A IS THE LIFE SAFETY / REFECTED CEILING
 PLAN; HOWEVER A SECOND 1.0A SHEET IS IN THE SUBMITTED
 PLAN SET.
  
 3. PROVIDE DIRECTIONAL INDICATOR FOR THE LAYOUT OF THE
 PROJECT FLOOR PLAN.
  
 4. IT IS INDICATED ON THE LIFE SAFETY PLAN AND THE
 POWER PLAN OF HORN STROBE NEAR A DOOR. DOES THIS
 BUILDING HAVE A FIRE ALARM SYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722