| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| ALL COMMENTS RELATE TO SHEET, UNLESS OTHERWISE NOTED. |
| ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} THE CURRENT CODE ARTICLES ARE LISTED ABOVE INDICATE |
| THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED ON |
| THE PLAN, 106.5 FBC. |
| |
| 2} NOTE #13 REGARDING GFI'S SHOULD BE REWORDED TO SHOW |
| COMPLIANCE WITH 680.22,POOL RECEPTACLES, AND |
| 210.8(A)(6),KITCHEN COUNTERTOP RECEPTACLES. |
| |
| 3} THE OCP FOR THE CONDENSING UNITS DO NOT CORRELATE |
| WITH THE MECHANICAL SPECIFICATION, SHEET M-1. |
| |
| 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| PER 210.11(C) (3), THERE ARE NONE LISTED ON THE PANEL |
| SCHEDULES |
| |
| 5} REGARDING THE REFERENCE TO GFI'S BEING WATER PROOF |
| ALTHOUGH NOT A VIOLATION, IF PART OF THE PERMITTED SET |
| OF PLANS THEY MUST BE INSTALLED, OR A REVISION WILL BE |
| MUST BE SUBMITTED TO MAKE A CHANGE IN THE FUTURE. |
| |
| 6} NOTE #2 IN THE "GENERAL ELECTRICAL NOTES" REFERS TO |
| TW WIRE. PLEASE NOTE THAT THE 60O TABLE MUST BE USED |
| FOR THESE CONDUCTORS IF THIS NOTE REMAINS ON THE PLAN. |
| |
| 7} 210.11(C) (1) SMALL-APPLIANCE BRANCH CIRCUITS IN |
| ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE |
| SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR |
| ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). ONLY ONE |
| IS LISTED ON THE PANEL SCHEDULE'S. |
| |
| 8} THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE |
| LEVEL OF ALTERATION PURSUANT TO SECTIONS 403, 404 AND |
| 405 OF THE EXISTING BUILDING CODE. PLEASE DECLARE SAME |
| ON THE PLAN. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |