 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE COMPLIANCE WITH 600.6 DISCONNECTING MEANS
 FOR THE SIGN.
  
 2} INDICATE HOW THE SIGN IS BEING FED ELECTRICALLT,
 PANEL DESIGNATION AND BRANCH CIRCUIT NUMBER , AMPERAGE
 ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  