Plan Review Notes
Plan Review Notes For Permit 09080161
Permit Number 09080161
Review Stop E
Sequence Number 2
Notes
Date Text
2009-10-08 09:58:47 
 ** TEMPORARY FAILED**
  
 ** WAITING FOR THE FOLLOWING INFORMATION.
  
 1) NOTE: CALL WAS PLACED TO PUBLIX CORPORATE OFFICE TO
 OBTAIN COPY OF CONTRACT FOR SCOPE OF WORK TO VERIFY
 VALUE.
 FBC 108.3
  
 2) NOTE: NEW REVISED ELECTRICAL/GENERATOR SITE PLANS
 WERE SUBMITTED. THE ENGINEER AS SIGNED AND SEALED ON
 SHEETS IS NOT THE ENGINEER AS LISTED ON TITLE BLOCKS AS
 THE RESPONSIBLE DESIGNER OF RECORD. A CALL WAS PLACED
 TO THE ENGINEER'S PHONE NUMBER AS LISTED ON TITLE BLOCK
 HOWEVER THIS NUMBER IS NO LONGER THE NUMBER OF THE
 ENGINEER OF RECORD.
 FS 471.025, FAC 61G15-23.002
  
  
  
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  