2009-08-27 08:08:37 | |
| ** DENIED REVIEW ** |
| |
| ** SPOKE TO PUBLIX MAIN OFFICE AND ALL FENCES AROUND |
| GENERATORS WILL BE RE-REVIEWED BY THE CORPORATE OFFICE. |
| PLANS WILL ALL NEED TO BE REVISED FOR MOST PROJECTS. |
| |
| 1) NOTE: PLEASE PROVIDE MINIMUM CLEARANCES FOR |
| GENERATOR PER 110.26. THE PLANS INDICATE 1FT 2INCHES. |
| PLEASE ALSO CHECK WITH THE MANUFACTURE AS THERE ARE |
| MINIMUM CLEARANCE REQUIREMENTS ALSO FOR VENTILATION. |
| 110.3,90.7 ETC |
| |
| 2) NOTE: MAY NOT SUBMIT PLANS DONE BY AN ENGINEER FOR |
| PERMITTING AND RECORD PLANS UNLESS SIGNED, DATED AND |
| SEALED BY SAID ENGINEER. |
| FS 471.025 |
| FAC61G15-23.002 |
| |
| 3) NOTE: PLEASE BE SURE TITLE BLOCK INCLUDES THE |
| CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL |
| FIRM. FS 481.221, FAC 61G1-16.004 |
| |
| 4) NOTE: PLEASE SEE PLANS ARE NOTING DESIGN PER 2004 |
| FBC, ASCE-7-02, 90MPH, EXPOSURE *C*. |
| PLEASE CHECK DESIGN. |
| THE WIND ZONE IN THE CITY OF WEST PALM BEACH IS 140MPH, |
| 3SEC GUST. |
| PLEASE ALSO KNOW AS OF MARCH 1ST, 2009 THE STATE OF |
| FLORIDA ADOPTED THE 2007 FBC WITH THE 2009 GLITCH |
| AMENDMENTS. |
| PLEASE KNOW THAT THERE WERE CHANGES IN EXPOSURE |
| CATEGORIES. |
| THIS JURISDICTION IS NOT REVIEWING FOR DESIGN OF FENCE |
| MEETING MINIMUM CODE HOWEVER PLANS SUBMITTED FOR |
| PERMITTING ARE REQUIRED TO CONTAIN CORRECT CODES. |
| PLEASE BE SURE TO VERIFY FOR PUBLIX CORPORATE OFFICES |
| FOR MINIMUM DESIGNS. |
| |
| 5) NOTE: PLEASE BE SURE TO COORDINATE PLANS. ELECTRICAL |
| SHEETS STATE 10FT 6INCHES ON FENCE AND SHEET PVC5 |
| STATES 10FT. |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2009-08-20 16:03:08 | GAVE TO DEWEY |