Plan Review Notes
Plan Review Notes For Permit 09080125
Permit Number 09080125
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-17 13:33:03 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SQUARE FOOTAGE AND LIGHTING POWER COMPLIANCE IN
 THE FLA/COM AND THE LIGHTING PERFORMANCE CALCULATIONS
 ON SHEET E-1.1DO NOT CORRELATE. 13-415,AB,5. THE DESIGN
 WATTS ARE OVER THE ALLOWABLE WATTS IN THE LIGHTING
 PERFORMANCE CALCULATION, SHEET E-1.1.
  
 2} 240.24(D) NOT IN VICINITY OF EASILY IGNITIBLE
 MATERIAL OVERCURRENT DEVICES SHALL NOT BE LOCATED IN
 THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS.
 EXAMPLES OF LOCATIONS WHERE COMBUSTIBLE MATERIALS MAY
 BE STORED ARE LINEN CLOSETS, PAPER STORAGE CLOSETS, AND
 CLOTHES CLOSETS.INDICATE WHAT MATERIALS ARE INTENDED TO
 BE STORED IN ROOM 105. ALSO SEE 110.26.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  