Plan Review Notes For Permit 09080089 |
Permit Number |
09080089 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-09-11 10:58:27 | *****FIRE-STAMPED***** | | | | BASED UPON FIRE MARSHAL CARSILLO'S PLAN REVIEW APPROVAL | | OF 9/10/2009, SHEETS LS-1, A-2.0, A-3.1, A-5.1, A-7.1, | | E-2.0, AND FA-1.0 & FA-2.0 WERE STAMPED, INITIALED, AND | | DATED. | 2009-09-10 14:10:29 | 550 SOUTH ROSEMARY AVENUE | | 0908080089 | | | | 1. CROWD MANAGEMENT CERTIFICATES ARE REQUIRES TO BE | | SUBMITTED TO THE FIRE MARSHAL'S OFFICE. ONE TRAINED | | CROWD MANAGER IS REQUIRED FOR EVERY 250 PERSONS. | | RESPONSE TO COMMENTS NARRATIVE INDICATES THAT CROWD | | MANAGEMENT TRAINING HAS ALREADY BEEN COMPLETED BY THE | | PROPOSED TENANT. | | | | 2. A SEPARATE FIRE ALARM CONTROL PANEL IS NOT REQUIRED | | FOR THIS TENANT SPACE. THE DESIRED ARRANGMENT IS TO | | CONNECT THE TENANT IMPROVEMENT SYSTEM TO THE MAIN FIRE | | ALARM CONTROL PANEL FOR THE BUILDING. THIS SYSTEM DOES | | NOT NEED TO BE PROPRIETARY TO THE TENANT SPACE. | | SEPARATE PLANS AND PERMITS REQUIRED PRIOR TO THE | | INSTALLATION. | | | | 3. THE UNISEX 115 RESTROOM IS MISSING A FIRE ALARM | | STROBE DEVICE. | | | | APPROVED PROVISO | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | |
|