Plan Review Notes For Permit 09080089 |
Permit Number |
09080089 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-09-11 12:17:03 | ** REDLINED PLANS ** | | | | | | 1) NOTE: OLD PREVIOUSLY SUBMITTED FORM B WAS STILL | | ATTACHED TO PLANS. THESE HAVE BEEN STAMPED *VOID*. | | | | 2) NOTE: THE 250AMP BREAKER NOTED ON HVPP SHALL BE | | VERIFIED IN FIELD. | | | | 3) NOTE: REDLINED ELECTRICAL PLANS TO SEE SHEET A5-5 | | FOR NEW RATED ROOM FOR 150 KVA TRANSFORMER. | | | | 4) NOTE: NO GROSS ERRORS ON LIGHTING PERFORMANCE | | CALCULATIONS PER 13-103.3 | | | | 5) NOTE: WENT OVER TENANT MAINS WITH JAKE LEAHY. ALL | | LABELING SHALL BE CLEAR, CONTRASTING BACK GROUNDS WITH | | MINIMUM OF 1 INCH LETTERING. ALL SIGNS SHALL BE | | PERMANENT. | | | | 6) NOTE: ALL LIGHTING SHALL MEET MINIMUM LEVELS FOR | | LIFE SAFETY. NO EGRESS LIGHTING SHALL DIM BELOW MINIMUM | | LIGHTING LEVELS. ALL LEVELS SHALL BE VERIFIED BEFORE | | OCCUPANCY. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|