Plan Review Notes
Plan Review Notes For Permit 09080089
Permit Number 09080089
Review Stop E
Sequence Number 2
Notes
Date Text
2009-09-11 12:17:03** REDLINED PLANS **
  
  
 1) NOTE: OLD PREVIOUSLY SUBMITTED FORM B WAS STILL
 ATTACHED TO PLANS. THESE HAVE BEEN STAMPED *VOID*.
  
 2) NOTE: THE 250AMP BREAKER NOTED ON HVPP SHALL BE
 VERIFIED IN FIELD.
  
 3) NOTE: REDLINED ELECTRICAL PLANS TO SEE SHEET A5-5
 FOR NEW RATED ROOM FOR 150 KVA TRANSFORMER.
  
 4) NOTE: NO GROSS ERRORS ON LIGHTING PERFORMANCE
 CALCULATIONS PER 13-103.3
  
 5) NOTE: WENT OVER TENANT MAINS WITH JAKE LEAHY. ALL
 LABELING SHALL BE CLEAR, CONTRASTING BACK GROUNDS WITH
 MINIMUM OF 1 INCH LETTERING. ALL SIGNS SHALL BE
 PERMANENT.
  
 6) NOTE: ALL LIGHTING SHALL MEET MINIMUM LEVELS FOR
 LIFE SAFETY. NO EGRESS LIGHTING SHALL DIM BELOW MINIMUM
 LIGHTING LEVELS. ALL LEVELS SHALL BE VERIFIED BEFORE
 OCCUPANCY.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  