Plan Review Notes
Plan Review Notes For Permit 09080089
Permit Number 09080089
Review Stop M
Sequence Number 1
Notes
Date Text
2009-08-10 21:00:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-2.0: PROVIDE SPACE BY SPACE VENTILATION
 CALCULATIONS BASED ON FLOOR PLAN AND USE OF INDIVIDUAL
 SPACES. EXAMPLE: FLOOR PLAN SHOWS MULTIPLE
 DINING/RESTAURANT AREAS AND BAR AREAS. THE OCCUPANT
 LOADS FOR BAR AREAS ARE CALCULATED AT A HIGHER RATE
 THAN FOR THE DINING AREAS. PROVIDE SPACE BY SPACE
 CALCULATIONS FOR BAR AREAS, DINING AREAS, STAGE AREAS,
 DANCE FLOOR AREAS IN ACCORDANCE WITH ASHRAE 62.1-2004
 TABLE 6-1.
  
 2. PAGE M-1.0: FLOOR PLAN SHOWS WHAT APPEARS TO BE A
 ROOF-MOUNTED EXHAUST FAN ABOVE WOMENS RESTROOM 139.
 THIS HAS NO LABEL ON PLANS. PLEASE IDENTIFY THIS AND
 ALL EQUIPMENT IN ACCORDANCE WITH FBC-M 304.11.
  
 3. PAGE M-1.0: PROVIDE THE CFM OF EACH EXHAUST GRILL IN
 WOMENS RESTROOM 139 TO DEMONSTRATE COMPLIANCE WITH
 ASHRAE 62.1-2004 TABLE 6-4.
  
 4. PAGE M-2.0: DUCT SMOKE DETECTOR SHALL BE CONNECTED
 TO THE BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH
 FBC-M 606.4.1.
  
 5, PAGE M-2.0: NEW RTU SHALL BE PROVIDED WITH AUXILIARY
 DRAIN PROTECTION VIA WATER LEVEL DETECTION DEVICE
 INSTALLED INTERNALLY ON THE PRIMARY DRAIN PAN IN
 ACCORDANCE WITH FBC-M 607.3.2.1.
  
 6. PROVIDE MANUFACTURER'S DATA FOR WIND RESTSTANCE
 CAPABILITIES OF PROPOSED NEW ROOFTOP EXHAUST FANS IN
 ACCORDANCE WITH FBC-M 301.12. ALSO, NO INSTALLATION
 DETAIL WAS PROVIDED FOR ROOFTOP EXHAUST FANS. PROVIDE
 ENGINEERED ATTACHMENT DETAIL FOR FANS AND RELATED CURBS
 OR MANUFACTURER'S INSTALLATION INSTRUCTIONS IF THEY ARE
 PART OF THE WIND RESISTANCE CERTIFICATION.
  
 7. PROVIDE MANUFACTURER'S DATA FOR WIND RESTSTANCE
 CAPABILITIES OF PROPOSED NEW ROOFTOP PACKAGE UNIT IN
 ACCORDANCE WITH FBC-M 301.12. ALSO, PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS IF THEY ARE
 PART OF THE WIND RESISTANCE CERTIFICATION.
  
 8. PAGE M-1.0: NOTE AT RATED STAIR ENCLOSURE CALLS FOR
 FIRE DAMPERS TO BE INSTALLED AT ALL "PENETRATIONS THRU
 MEZZANINE." PLEASE CLARIFY DESIGN IN THIS AREA AS NO
 MEZZANINE OR FIRE RATED ASSEMBLY ASSOCIATED WITH A
 MEZZANINE IS INDICATED ON PLANS. THE NOTE APPEARS
 INSIDE A RATED STAIR EXIT ENCLOSURE. NO PENETRATIONS OF
 EXIT ENCLOSURES ARE PERMITTED IN ACCORDANCE WITH FBC-B
 1020.1.2. ALSO, IF ANY FIRE DAMPERS ARE REQUIRED TO BE
 INSTALLED IN RELATION TO THIS PROJECT, THEY MUST BE
 SHOWN AND CLEARLY IDENTIFIED ON PLANS IN ACCORDANCE
 WITH FBC-M 607.8.
  
 9. A TEST AND BALANCE REPORT SHALL BE PROVIDED TO THE
 FIELD INSPECTOR AT TIME OF FINAL INSPECTION TO VERIFY
 REQUIRED VENTILATION RATES ARE BEING PROVIDED IN
 ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]