2009-08-10 21:00:12 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PAGE M-2.0: PROVIDE SPACE BY SPACE VENTILATION |
| CALCULATIONS BASED ON FLOOR PLAN AND USE OF INDIVIDUAL |
| SPACES. EXAMPLE: FLOOR PLAN SHOWS MULTIPLE |
| DINING/RESTAURANT AREAS AND BAR AREAS. THE OCCUPANT |
| LOADS FOR BAR AREAS ARE CALCULATED AT A HIGHER RATE |
| THAN FOR THE DINING AREAS. PROVIDE SPACE BY SPACE |
| CALCULATIONS FOR BAR AREAS, DINING AREAS, STAGE AREAS, |
| DANCE FLOOR AREAS IN ACCORDANCE WITH ASHRAE 62.1-2004 |
| TABLE 6-1. |
| |
| 2. PAGE M-1.0: FLOOR PLAN SHOWS WHAT APPEARS TO BE A |
| ROOF-MOUNTED EXHAUST FAN ABOVE WOMENS RESTROOM 139. |
| THIS HAS NO LABEL ON PLANS. PLEASE IDENTIFY THIS AND |
| ALL EQUIPMENT IN ACCORDANCE WITH FBC-M 304.11. |
| |
| 3. PAGE M-1.0: PROVIDE THE CFM OF EACH EXHAUST GRILL IN |
| WOMENS RESTROOM 139 TO DEMONSTRATE COMPLIANCE WITH |
| ASHRAE 62.1-2004 TABLE 6-4. |
| |
| 4. PAGE M-2.0: DUCT SMOKE DETECTOR SHALL BE CONNECTED |
| TO THE BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH |
| FBC-M 606.4.1. |
| |
| 5, PAGE M-2.0: NEW RTU SHALL BE PROVIDED WITH AUXILIARY |
| DRAIN PROTECTION VIA WATER LEVEL DETECTION DEVICE |
| INSTALLED INTERNALLY ON THE PRIMARY DRAIN PAN IN |
| ACCORDANCE WITH FBC-M 607.3.2.1. |
| |
| 6. PROVIDE MANUFACTURER'S DATA FOR WIND RESTSTANCE |
| CAPABILITIES OF PROPOSED NEW ROOFTOP EXHAUST FANS IN |
| ACCORDANCE WITH FBC-M 301.12. ALSO, NO INSTALLATION |
| DETAIL WAS PROVIDED FOR ROOFTOP EXHAUST FANS. PROVIDE |
| ENGINEERED ATTACHMENT DETAIL FOR FANS AND RELATED CURBS |
| OR MANUFACTURER'S INSTALLATION INSTRUCTIONS IF THEY ARE |
| PART OF THE WIND RESISTANCE CERTIFICATION. |
| |
| 7. PROVIDE MANUFACTURER'S DATA FOR WIND RESTSTANCE |
| CAPABILITIES OF PROPOSED NEW ROOFTOP PACKAGE UNIT IN |
| ACCORDANCE WITH FBC-M 301.12. ALSO, PROVIDE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS IF THEY ARE |
| PART OF THE WIND RESISTANCE CERTIFICATION. |
| |
| 8. PAGE M-1.0: NOTE AT RATED STAIR ENCLOSURE CALLS FOR |
| FIRE DAMPERS TO BE INSTALLED AT ALL "PENETRATIONS THRU |
| MEZZANINE." PLEASE CLARIFY DESIGN IN THIS AREA AS NO |
| MEZZANINE OR FIRE RATED ASSEMBLY ASSOCIATED WITH A |
| MEZZANINE IS INDICATED ON PLANS. THE NOTE APPEARS |
| INSIDE A RATED STAIR EXIT ENCLOSURE. NO PENETRATIONS OF |
| EXIT ENCLOSURES ARE PERMITTED IN ACCORDANCE WITH FBC-B |
| 1020.1.2. ALSO, IF ANY FIRE DAMPERS ARE REQUIRED TO BE |
| INSTALLED IN RELATION TO THIS PROJECT, THEY MUST BE |
| SHOWN AND CLEARLY IDENTIFIED ON PLANS IN ACCORDANCE |
| WITH FBC-M 607.8. |
| |
| 9. A TEST AND BALANCE REPORT SHALL BE PROVIDED TO THE |
| FIELD INSPECTOR AT TIME OF FINAL INSPECTION TO VERIFY |
| REQUIRED VENTILATION RATES ARE BEING PROVIDED IN |
| ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2. |
| |