2009-08-20 14:45:18 | 550 SOUTH ROSEMARY AVENUE |
| PERMIT # 09080089 |
| INTERIOR BUILD-OUT OF EXISTING RESTAURANT. BUILD-OUT IS |
| PROVIDED PER PROVIDED PLANS. |
| |
| 1. CONSTRUCTION, DEMOLITION, AND RENOVATION IS TO |
| COMPLY WITH NFPA 241. |
| |
| 2. EXITS ARE TO REMAIN CLEAR AND ACCESSIBLE. |
| |
| 3. DERBIS IS TO BE REMOVED FROM THE SITE DAILY. |
| |
| 4. CHAIRS APPEAR TO BE TOO CLOSE TOGETHER IN BAR AND |
| DINING SEATING, SECTION 110. |
| |
| 5. IS THE EXISTING OUTSIDE COVERED RESTARAUNT AREA FIRE |
| SPRINKLER PROTECTED, SECTION 201. |
| |
| 6. TACTILE SIGNAGE REQUIRED AT EXIT LOCATIONS. |
| |
| 7. NO STORAGE OR ACCESS PERMITTED UNDER THE PLATFORM. |
| |
| 8. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR ALL NEW HANDRAILS AND GUARDRAILS. |
| |
| 9. CROWD MANAGEMENT TRAINING IS REQUIRED FOR THE |
| FACILITY. ONE CROWD MANAGER IS REQUIRED FOR EVERY 250 |
| PERSONS. PLEASE GO TO MARYLAND STATE FIRE MARSHALS |
| WEB-SITE AND CLICK ON THE ICON FOR ON-LINE CROWD |
| MANAGEMENT TRAINING. PLEASE WATCH THE VIDEO, TAKE THE |
| TEST, AND SUBMIT COPIES OF THE CERTIFICATE TO THIS |
| OFFICE. |
| |
| 10. ALL EXISTING HOODS SHALL COMPLY WITH NFPA 96. |
| |
| 11. NEW FABRIC CANOPY SHOWN ON PAGE A-4.0 SHALL BE FIRE |
| RETARDANT. |
| |
| 12. PLEASE INDICATE ON DRAWINGS THE LOCATIONS OF ALL |
| FIRE ALARM SIGNALING AND INITIATING DEVICES. PLEASE |
| INDICATE ANY NEW OR EXISTING DEVICES. |
| |
| 13. ALL DOORS THAT COULD BE CONFUSED AS EXITS SHOULD BE |
| MARKED "NO EXIT". |
| |
| 14. PROPER LIGHTING LEVELS ARE REQUIRED FOR STAIR |
| LOCATIONS. |
| |
| |
| DENIED |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |