2009-08-19 19:34:36 | |
| |
| |
| |
| |
| |
| ** DENIED REVIEW ** |
| |
| ** PLANS ARE MISSING INFORMATION NOT YET SHOWN. THERE |
| ARE SEVERAL ITEMS WHICH CAN NOT BE REVIEWED FOR MINIMUM |
| CODE COMPLIANCE AT THIS TIME. THERE MAY VERY WELL BE |
| NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| POSSIBLY BE MADE AT THIS TIME> SEE NOTES. |
| |
| 1) NOTE: PLEASE SEE THAT SOME OF THE CODE INFORMATION |
| FOR MINIMUM DESIGNS LISTED ON COVER SHEET IS NOT |
| CORRECT. |
| PLANS INDICATE 2004 FBC FOR CHAPTER 11. HOWEVER AS OF |
| MARCH 1ST, 2009 THE STATE OF FLORIDA ADOPTED THE 2007 |
| FBC W/ 2009 SUPPLEMENTS. THIS INCLUDES CHAPTER 11 UNDER |
| THE 2007 FBC. |
| THE PLANS STATE THE 2004 FLORIDA FIRE PREVENTION CODE |
| HOWEVER AS OF DECEMBER 31ST, 2008 THE STATE ADOPTED THE |
| 2007 FFPC. PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| 69A-60 |
| PLEASE ALSO SEE THE SECTIONS 69A-60.003 AND .004 AS THE |
| FOLLOWING NFPA-1 AND NFPA-101 ( LIFE SAFETY CODE ) IS |
| ACTUALLY THE 2006 EDITIONS. PLANS STATE THE 2003 |
| EDITION OF NFPA-101. |
| |
| ** LIGHTING CONTROLS STATES TO MEET THE FBC WITH 2006 |
| SUPPLEMENTS. AS NOTED ABOVE THE 2006 SUPPLEMENTS WOULD |
| BE UNDER THE 2004 FBC. NOT THE CURRENT 2007 FBC WITH |
| 2009 SUPPLEMENTS. |
| |
| 2) NOTE: PLEASE PROVIDE SIGNED CONTRACTS OR ADJUST |
| VALUE FOR COMPLETE SCOPE OF WORK AS THE APPLIED VALUE |
| IS LOW. THE APPLIED VALUE SHALL INCLUDE ALL LABOR, |
| MATERIALS, PERMANENTLY INSTALLED EQUIPMENT, DESIGN COST |
| ETC EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. |
| FBC 108.3 |
| THE APPLIED VALUE OF $200K FOR THE ENTIRE PROJECT IS |
| LOW. |
| |
| 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS FOR NEW BEING INSTALLED ALONG WITH |
| EXISTING. PLEASE SEE 13-415.AB.5, 13-415.B. THE |
| SUBMITTED SINGLE FORM B IS NOT ACCEPTABLE FOR SCOPE OF |
| WORK AS SHOWN. FORM 400B IS PERMITTED HOWEVER THIS |
| WOULD REQUIRE THIS SAME FOR EACH AND EVERY SPACE IN THE |
| TENANT SPACE. |
| PLEASE SEE 13-400.0.B.4 WHEN NOT MEETING THE DEFINITION |
| OF *RENOVATION* OF A BUILDING THEN ALL NEW INSTALLED |
| MUST MEET PRESCRIPTIVE REQUIREMENTS. SEE SECTIONS NOTED |
| AND SEE SECTION 202 FOR DEFINITIONS. |
| THE SUBMITTED INFORMATION ON PLANS IS OVER THE LIGHTING |
| ALLOWANCES PERMITTED. PLEASE KNOW THE SPACE BY SPACE IS |
| JUST THAT. SPACE BY SPACE ALLOWANCES MAY NOT USE FAMILY |
| DINING ALLOWANCES FOR THE BATHROOMS, STORAGE ROOMS, |
| ETC. THE BAR LOUNGE ALLOWANCES MAY NOT BE USED FOR THE |
| OTHER TYPES OF AREAS. ALL SEPARATE SPACE MUST BE |
| DESIGNATED. |
| PLEASE ALSO KNOW THAT THAT LIGHTING ALLOWANCE WATTAGE |
| SHOWN ON LIGHTING CONTROL PANELS ON SHEET E-5.0 IS |
| HIGHER THAN THE DESIGN ON SHEET E-4.0. |
| PLEASE KNOW AT THIS TIME DESIGN IS SUBSTANTIALLY OVER |
| THE MAXIMUM ALLOWANCES PERMITTED BY THE ENERGY CODE. |
| THIS IS BASED ON THE INFORMATION STATED AND SHOWN ON |
| PLANS. |
| ** FIXTURE WATTAGES ARE NOT BASED ON LIGHT BULBS, IT |
| MUST BE FIGURED PER FIXTURE. * FIXTURE O FOR ONLY ONE |
| EXAMPLE* |
| |
| ** IF THERE ARE QUESTIONS, IT IS RECOMMENDED TO CONTACT |
| REVIEWER. |
| |
| 4) NOTE: PLEASE SEE NFPA-101 7.10.8.3.1, .2. ANY EXIT |
| WHICH COULD BE MISTAKEN FOR AN EXIT IN AN EMERGENCY |
| SHALL BE IDENTIFIED WITH SIGNS PER SECTIONS NOTED. |
| PLEASE PLACE NOTES ON ELECTRICAL PLANS ALONG WITH LIFE |
| SAFETY PLANS FOR WORDS OF NO EXIT IN MINIMUM SIZE |
| REQUIREMENTS. |
| |
| 5) NOTE: PLEASE PROVIDE PHOTO-METRIC LEVELS FOR ALL |
| DESIGNATED EGRESS PATHS UNDER NORMAL AND EMERGENCY |
| CONDITIONS. PLEASE KEEP IN MIND THAT NO LIGHTING |
| CONTROL OR DIMMING SYSTEM IS PERMITTED TO DIMINISH |
| LIGHTING LEVELS BELOW THE MINIMUM. THIS SHALL BE SET |
| AND SHALL NOT BE OVER RIDDEN. PLEASE SEE THAT ALL STAIR |
| AREAS/STEPS SHALL CONTAIN THE MINIMUM OF 10FT CANDLES |
| UNDER NORMAL AND IS PERMITTED TO GO DOWN TO 1FT CANDLE |
| UNDER AN EMERGENCY. |
| PLEASE SEE 7.8.1.3, 7.9.1.2, .2.2. PLEASE ALSO SEE |
| 7.8.1.2.2 FOR ANY REQUIRED EGRESS LIGHTING ON OCCUPANCY |
| CONTROLS WHICH SHALL FAIL SAFE *ON*. |
| |
| 6) NOTE: THE RISER, LOAD CALCULATIONS AND PANEL |
| SCHEDULES SUBMITTED ALL NEED TO BE COMPLETE WITH THE |
| FOLLOWING INFORMATION FOR REVIEW. |
| FOR EXAMPLE: |
| |
| A) PLEASE SEE RISER ON SHEET E-7.0 WHICH CLEARLY |
| INDICATES PANEL *HVPP* FEEDING 150KVA TRANSFORMER WITH |
| A 250AMP BREAKER. HOWEVER PANEL SCHEDULE FOR THIS SAME |
| *HVPP* DOES NOT LIST ANY SUCH BREAKER OR FEED TO THE |
| TRANSFORMER.??? |
| |
| B) PLEASE PROVIDE INFORMATION FOR WHERE *LVMDP* IS |
| BEING FED FROM. |
| |
| C) PLEASE SEE *HVPP* WHICH DOES NOT INCLUDE ANY OF THE |
| LOADS FOR THE LVMDP SUCH AS LIGHTING. |
| |
| D) THERE IS NO INFORMATION ON WHERE PANELS *H1 OR H2* |
| ARE BEING FED FROM. ARE THESE FROM OTHER SERVICES? ARE |
| THESE FROM MULTIPLE TENANT METERS? |
| ARE MAINS GROUPED? LABELED? BONDED SERVICES? ETC |
| |
| E) RISER INDICATES #3 AWG AS THE SIZE OF THE NEW |
| FEEDERS TO THE NEW PANEL *C* YET *LVMDP* INDICATES |
| *3/0*AWG. THIS IS SUBSTANTIALLY DIFFERENT. |
| PLEASE COORDINATE. |
| |
| F) RISER INDICATES THAT PANEL K IS BEING FED FROM THE |
| TRANSFORMER AND PANEL H1. HOWEVER PANEL H1 STATES A |
| FEED TO PANEL *P* NOT TO PANEL *K*. |
| |
| G) PANEL *P* IS SHOWN WITH FEED-THRU LUGS ON SCHEDULE |
| HOWEVER THIS PANEL IS NOT SHOWN ON RISER FEEDING THRU |
| TO ANY OTHER PANEL. IS THIS THE CASE? |
| |
| H) TRACK LIGHTING LOADS ARE NOT SHOWN PER 220.43B |
| |
| I) SHOW WINDOW LOADS NOT SHOWN PER 220.43A |
| |
| J) SHOW LOCATIONS OF ALL TRANSFORMERS ON |
| PLANS.450.13,450.21,240.21, 310.16 ETC TO BE REVIEWED |
| ALONG WITH 110.26, 450.9. |
| RISER INDICATES THE 150KVA TRANSFORMER WHICH FEEDS FROM |
| HVPP TO LVMDP, YET THE PLANS DOES NOT INDICATE THIS |
| TRANSFORMER ANYWHERE NEAR THE PROXIMITY OF EITHER OF |
| THESE. SEE 240.21 FOR TAPPED CONDUCTORS. |
| |
| K) PLEASE PROVIDE ALL CONDUCTORS ON THE SECONDARY SIDE |
| OF THE TRANSFORMERS. SEE 240.21,310.16,240.4. |
| |
| *** PLEASE COORDINATE ALL OF THE ELECTRICAL SYSTEMS AND |
| SUBMIT A COMPLETE RISER WITH LOAD CALCULATIONS AND |
| SIZES FOR ALL SYSTEMS. |
| SEVERAL EXAMPLES ARE GIVEN ABOVE TO SOME OF THE ITEMS |
| WHICH ARE NOT COORDINATED OR PROVIDED. THERE ARE MANY |
| ITEMS WHICH CAN NOT BE REVIEWED FOR MINIMUM CODE |
| COMPLIANCE AT THIS TIME. THESE ARE SOME EXAMPLES ONLY |
| AND ARE IN NO WAY ALL. |
| |
| PLEASE SEE 220, 230.70, 230.71,230.72, 230.2E,310.16, |
| 240.21 ETC. THERE ARE TOO MANY SECTIONS TO NOTE. |
| FBC 106.1.1,106.1.2,106.3.5.1.2 FOR CLARITY, |
| COORDINATION OF RECORD PLANS. |
| |
| 7) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2 AND .1.3 FOR |
| LIGHTING CONTROLS. PLEASE SEE SECTION 13-415.AB.1.3 |
| SPECIFICALLY FOR CONTROLS. |
| ALSO SEE ITEMS LIKE THE FAN LIGHTS WHICH ARE SHOWN ON |
| FAN CONTROLS. |
| OTHER FIXTURES SUCH AS FIXTURES F AND OTHER LOCATIONS |
| WHICH INDICATE OVER RIDES AS STANDARD SINGLE POLE |
| SWITCH PER SYMBOL LEGEND WHICH IS NOT PERMITTED. |
| |
| 8) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING |
| CONTROLS. |
| |
| |
| 9) NOTE: PLEASE SEE 210.8B2 FOR WET BAR AND KITCHEN |
| AREA GFI PROTECTION REQUIRED. |
| |
| 10) NOTE: PLEASE SEE NOTES ON E-4.0 WHICH INDICATE CODE |
| SECTIONS FROM PREVIOUS FLORIDA BUILDING CODE. SUCH AS |
| SECTIONS NOTED: 13-415.1.ABC.3. |
| |
| 11) NOTE: PLEASE SHOW ALL DEVICES FOR FIRE ALARM HORNS, |
| STROBES, ETC MEETING ADA PER FBC CHAPTER 11. EVEN AS |
| THE FA SYSTEM/SCOPE IS UNDER SEPARATE PERMIT, PER FS |
| 633 MINIMUM DESIGN FOR FIRE AND LIFE SAFETY SHALL BE ON |
| BASE PLANS. PLEASE SEE FBC 11-4.28.1,.2 AND .3. |
| |
| AS NOTED ABOVE, THERE ARE SEVERAL ITEMS IN NEED OF |
| COORDINATION AND INFORMATION TO BE SUBMITTED FOR |
| REVIEW. THERE MAY BE NEW COMMENTS ON THE NEXT REVIEW. |
| |
| ** PER BUILDING OFFICIAL PLANS ARE NO LONGER RELEASED. |
| ALL SHEETS TO BE REVISED OR CHANGED OUT IN THIS OFFICE. |
| |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| |