2009-08-10 13:19:27BUILDING PLAN REVIEW
 PERMIT: 09080089
 ADD: 550 S ROSEMARY SUITE# 236 "BB KING"
 CONT: WATLEE CONSTRUCTION
 TEL: (772)2230604
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: CRAIG MOSSEY P. A. (561)447-2911
  
 MEP: BUCHANAN P. E. CONSULTING, KAMAL AL HALABI P. E.
 (954)950-2232
 TNOTE4: SHEET A-0.0 ALTHOUGH THIS BUILDING IS
 CONSIDERED A THRESHOLD BUILDING UNDER 553.79 ,NO
 THRESHOLD INSPECTION REPORT NOR THRESHOLD INSPECTOR
 WILL BE REQUIRED. THE BUILDING OFFICIAL REVIEWED 553.79
 AND WITHIN THE LANGUAGE FOR A THRESHOLD BUILDING THE
 INSPECTION REPORT AND INSPECTOR ARE REQUIRED "WHEN
 CONSTRUCTING" NOT REMODELING.
  
 1ST REVIEW
 ACTION:
  
 1) SHEET LS-1.0 ROOM# 102:
 1A) THE OCCUPANT LOAD FOR THIS ROOM IS OFF, PLANS ARE
 INDICATED AS 32 WHERE AS THERE ARE 44 ACTUAL SEATS,
 PLEASE CORRECT.106.1.2 ADDITIONAL INFORMATION, THIS
 WILL EFFECT ONE OF THE EXIT WAYS WITH THE ADDITIONAL
 LLOADING.
  
 1B) COMPLIED.
  
 2) SHEET LS-1.0 TWO AREAS OF CONCERN FOR OCCUPANT
 LOADING IS THE BENCH SEATINGIS THE BENCH OR BOOTH STYLE
 SEATING IN BOTH ROOMS 110 AND 111 PLEASE PROVIDE A
 BREAK DOWN OF OCCUPANTS FOR THESE ROOM AS PEROCCUPANTS
 IN CHAIRS AND BENCH OR BOOTH TYPE SEATING. 1004.7.
 AGAIN THIS MAY EFFECT THE EXIT PATERNS FOR THESE AREAS.
  
 3A) SHEET LS-1.0 INDICATES ACCESSIBLE SEATING IN ROOM
 100, 102 AND 201. I DON'T BELIEVE THERE WERE ANY
 ACCESSIBLE SEATING INDICATED IN THE THEATER SECTION .
 11-2.2 EQUIVALENT FACILITATION. DEPARTURES FROM
 PARTICULAR TECHNICAL AND SCOPING REQUIREMENTS OF THIS
 CODE BY THE USE OF OTHER DESIGNS AND TECHNOLOGIES ARE
 PERMITTED WHERE THE ALTERNATIVE DESIGNS AND
 TECHNOLOGIES USED WILL PROVIDE SUBSTANTIALLY EQUIVALENT
 OR GREATER ACCESS TO AND USABILITY OF THE FACILITY.
  
 DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY
 OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE
 THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN
 ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS
 OF THE ADA.
  
 3B) 11-4.32.2 SEATING. IF SEATING SPACES FOR PEOPLE IN
 WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR COUNTERS,
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2.4 SHALL
 BE PROVIDED. SUCH CLEAR FLOOR SPACE SHALL NOT OVERLAP
 KNEE SPACE BY MORE THAN 19 INCHES (485 MM) (SEE FIGURE
 45).
  
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY
 REFERENCE SECTION 11-4.1 SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE FOLLOWING
 REQUIREMENTS:
  
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
  
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
  
  
 4) SHEET LS-1.0 FIRE EXTINGUISHERS THREE ARE INDICATED
 ON THE PLANS LOCATED IN ROOMS 107, KITCHEN, 124 SERVICE
 AREA AND NEW SERVICE BAR BY DOOR 13. IT APPEARS THERE
 ARE NO EXTINGUISHERS BY TTHE EXISTING EXTERIOR DINING
 AREA 202OR NEW BAR 103. 906.1 GENERAL. PORTABLE FIRE
 EXTINGUISHERS SHALL BE PROVIDED IN OCCUPANCIES AND
 LOCATIONS AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE. SHEET A-2.0 HAS A NOT ABOUT FIRE EXTINGUISHERS TO
 BE LOCATED MAXIMUM 75' BETWEEN FIRE EXTINUISHERS.
  
 5A) SHEET A-2.0 INDICATES IN THE WALL LEGEND A WALL
 TYPE X1 WITH USE FOR A MECHANICAL PLATFORM ABOVE. SHEET
 M-1.0 INDICATES A MEZZANINE ABOVE THE STAIRWAY AND
 NOTE:
 ALL PENETRATIONSTHROUGH THE MEZZANINE SHALL HAVE A FIRE
 DAMPER. PLEASE PROVIDE ADDITIONAL INFORMATION ABOUT A
 MEZZANINE LEVEL, HOW YOU GAIN ACCESS AND WHERE IS ITS
 LOCATION?
 106.1.2. SHEET A-2.2 NEW WALLS SURROUNDING THE KITCHEN
 AND RESTROOMS APPEAR TO BE BUILT WITH THE DESINATION OF
 "A,B & H" WHAT WALL TYPE ARE THESE, THE WALL LEGEND ON
 A-2.0 DOES NOT INDICATE SUCH WALL TYPES?
  
 5) SHEET M-1.0 INDICATES WHAT APPEARS TO BE A DUCT THAT
 PASSES DOWN INTO THE RATED VERTICAL STAIRWELL EXIT?
 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 712. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 6) SHEET M-1.0 DOES NOTE NEW ROOF TOP UNITS. PLEASE
 REVIEW 301.13 FBC MECHANICAL. WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS
 AS DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
2009-08-08 11:02:58BUILDING PLAN REVIEW
 PERMIT: 09080089
 ADD: 550 S ROSEMARY SUITE# 236 "BB KING"
 CONT: WATLEE CONSTRUCTION
 TEL: (772)2230604
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: CRAIG MOSSEY P. A. (561)447-2911
  
 MEP: BUCHANAN P. E. CONSULTING, KAMAL AL HALABI P. E.
 (954)950-2232
 TNOTE4: SHEET A-0.0 ALTHOUGH THIS BUILDING IS
 CONSIDERED A THRESHOLD BUILDING UNDER 553.79 ,NO
 THRESHOLD INSPECTION REPORT NOR THRESHOLD INSPECTOR
 WILL BE REQUIRED. THE BUILDING OFFICIAL REVIEWED 553.79
 AND WITHIN THE LANGUAGE FOR A THRESHOLD BUILDING THE
 INSPECTION REPORT AND INSPECTOR ARE REQUIRED "WHEN
 CONSTRUCTING" NOT REMODELING.
  
 1ST REVIEW
 ACTION:
  
 1) SHEET LS-1.0 ROOM# 102:
 1A) THE OCCUPANT LOAD FOR THIS ROOM IS OFF, PLANS ARE
 INDICATED AS 32 WHERE AS THERE ARE 44 ACTUAL SEATS,
 PLEASE CORRECT.106.1.2 ADDITIONAL INFORMATION, THIS
 WILL EFFECT ONE OF THE EXIT WAYS WITH THE ADDITIONAL
 LLOADING.
  
 1B) FROM TTHE FARTHEST SEAT LEFT OF THE DOORWAY TO THE
 POINT WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS
 OF EGRESS EXCEEDS 30'.
 1014.4.3.3 TABLE AND SEATING AISLE ACCESSWAY LENGTH.
 THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY SHALL
 NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT
 WHERE A
 PERSON HAS A CHOICE OF TWO OR MORE PATHS OF EGRESS
 TRAVEL TO SEPARATE EXITS.
  
 2) SHEET LS-1.0 TWO AREAS OF CONCERN FOR OCCUPANT
 LOADING IS THE BENCH SEATINGIS THE BENCH OR BOOTH STYLE
 SEATING IN BOTH ROOMS 110 AND 111 PLEASE PROVIDE A
 BREAK DOWN OF OCCUPANTS FOR THESE ROOM AS PEROCCUPANTS
 IN CHAIRS AND BENCH OR BOOTH TYPE SEATING. 1004.7.
 AGAIN THIS MAY EFFECT THE EXIT PATERNS FOR THESE AREAS.
  
 3A) SHEET LS-1.0 INDICATES ACCESSIBLE SEATING IN ROOM
 100, 102 AND 201. I DON'T BELIEVE THERE WERE ANY
 ACCESSIBLE SEATING INDICATED IN THE THEATER SECTION .
 11-2.2 EQUIVALENT FACILITATION. DEPARTURES FROM
 PARTICULAR TECHNICAL AND SCOPING REQUIREMENTS OF THIS
 CODE BY THE USE OF OTHER DESIGNS AND TECHNOLOGIES ARE
 PERMITTED WHERE THE ALTERNATIVE DESIGNS AND
 TECHNOLOGIES USED WILL PROVIDE SUBSTANTIALLY EQUIVALENT
 OR GREATER ACCESS TO AND USABILITY OF THE FACILITY.
  
 DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY
 OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE
 THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN
 ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS
 OF THE ADA.
  
 3B) 11-4.32.2 SEATING. IF SEATING SPACES FOR PEOPLE IN
 WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR COUNTERS,
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2.4 SHALL
 BE PROVIDED. SUCH CLEAR FLOOR SPACE SHALL NOT OVERLAP
 KNEE SPACE BY MORE THAN 19 INCHES (485 MM) (SEE FIGURE
 45).
  
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY
 REFERENCE SECTION 11-4.1 SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE FOLLOWING
 REQUIREMENTS:
  
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
  
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
  
  
 4) SHEET LS-1.0 FIRE EXTINGUISHERS THREE ARE INDICATED
 ON THE PLANS LOCATED IN ROOMS 107, KITCHEN, 124 SERVICE
 AREA AND NEW SERVICE BAR BY DOOR 13. IT APPEARS THERE
 ARE NO EXTINGUISHERS BY TTHE EXISTING EXTERIOR DINING
 AREA 202OR NEW BAR 103. 906.1 GENERAL. PORTABLE FIRE
 EXTINGUISHERS SHALL BE PROVIDED IN OCCUPANCIES AND
 LOCATIONS AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE. SHEET A-2.0 HAS A NOT ABOUT FIRE EXTINGUISHERS TO
 BE LOCATED MAXIMUM 75' BETWEEN FIRE EXTINUISHERS.
  
 5A) SHEET A-2.0 INDICATES IN THE WALL LEGEND A WALL
 TYPE X1 WITH USE FOR A MECHANICAL PLATFORM ABOVE. SHEET
 M-1.0 INDICATES A MEZZANINE ABOVE THE STAIRWAY AND
 NOTE:
 ALL PENETRATIONSTHROUGH THE MEZZANINE SHALL HAVE A FIRE
 DAMPER. PLEASE PROVIDE ADDITIONAL INFORMATION ABOUT A
 MEZZANINE LEVEL, HOW YOU GAIN ACCESS AND WHERE IS ITS
 LOCATION?
 106.1.2. SHEET A-2.2 NEW WALLS SURROUNDING THE KITCHEN
 AND RESTROOMS APPEAR TO BE BUILT WITH THE DESINATION OF
 "A,B & H" WHAT WALL TYPE ARE THESE, THE WALL LEGEND ON
 A-2.0 DOES NOT INDICATE SUCH WALL TYPES?
  
 5) SHEET M-1.0 INDICATES WHAT APPEARS TO BE A DUCT THAT
 PASSES DOWN INTO THE RATED VERTICAL STAIRWELL EXIT?
 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 712. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 6) SHEET M-1.0 DOES NOTE NEW ROOF TOP UNITS. PLEASE
 REVIEW 301.13 FBC MECHANICAL. WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS
 AS DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved