Plan Review Notes
Plan Review Notes For Permit 09080087
Permit Number 09080087
Review Stop B
Sequence Number 1
Notes
Date Text
2009-08-06 10:57:54****PROVISO****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 CONTRACTOR TO SUBMIT A REVISED INSTALLATION SCHEDULE
 (REVISION) OR PROVIDE SIGNED, SEALED ORIGINAL
 ENGINEERING TO JUSTIFY PROPOSED DESIGN PRESSURES
  
 FBC1003.6, MEANS OF EGRESS CONTINUITY, CANNOT BLOCK
 MAIN ENTRANCE WITH PANELS. (OPENINGS 4 & 5 HAVE BEEN
 REMOVED)
  
 THE INSTALLATION SCHEDULE SUBMITTED WAS BASED ON DESIGN
 PRESSURE OF -33PSF. DESIGN PRESSURES RUN BY COMPOUTER
 PROGRAM RANGED FROM -29.4 TO -33.6.
  
 THE DESIGN PRESSURES GENERATED BY THE COMPUTER SOFTWARE
 YOU ARE USING DO NOT COMPLY WITH FBC R301, FBC1609,
 FAC61G15. ENGINEERING SOFTWARE IS TO INCLUDE THE
 COMPANY NAME AND VERSION NUMBER. THE DESIGN PRESSURES
 GENERATED ARE TOO LOW, SEE ASCE7-05.
  
 REVISION MUST BE REVIEWED PRIOR TO FIRST INSPECTION
  
 ISSUED AT CONTRACTOR'S RISK
  
  
  
  
  