Plan Review Notes For Permit 09080087 |
Permit Number |
09080087 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-08-06 10:57:54 | ****PROVISO**** | | ****REVISION REQUIRED**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | CONTRACTOR TO SUBMIT A REVISED INSTALLATION SCHEDULE | | (REVISION) OR PROVIDE SIGNED, SEALED ORIGINAL | | ENGINEERING TO JUSTIFY PROPOSED DESIGN PRESSURES | | | | FBC1003.6, MEANS OF EGRESS CONTINUITY, CANNOT BLOCK | | MAIN ENTRANCE WITH PANELS. (OPENINGS 4 & 5 HAVE BEEN | | REMOVED) | | | | THE INSTALLATION SCHEDULE SUBMITTED WAS BASED ON DESIGN | | PRESSURE OF -33PSF. DESIGN PRESSURES RUN BY COMPOUTER | | PROGRAM RANGED FROM -29.4 TO -33.6. | | | | THE DESIGN PRESSURES GENERATED BY THE COMPUTER SOFTWARE | | YOU ARE USING DO NOT COMPLY WITH FBC R301, FBC1609, | | FAC61G15. ENGINEERING SOFTWARE IS TO INCLUDE THE | | COMPANY NAME AND VERSION NUMBER. THE DESIGN PRESSURES | | GENERATED ARE TOO LOW, SEE ASCE7-05. | | | | REVISION MUST BE REVIEWED PRIOR TO FIRST INSPECTION | | | | ISSUED AT CONTRACTOR'S RISK | | | | | | | | | | |
|