2009-08-05 16:55:49RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PERMIT APPLICATION DESCRIBES "MODIFIED BITUMEN ROOF
 SYSTEM OVER WOOD DECK" ONLY. KEY PLAN SUBMITTED SHOWS
 THE MAIN ROOF AS PITCHED ROOF. ALSO, THERE IS A PRODUCT
 APPROVAL SUBMITTED FOR SHINGLES. CLARIFY SCOPE OF WORK.
 SPECIFY ROOF PITCH FOR SHINGLES. SPECIFY TOTAL AREA FOR
 SHINGLES AND TOTAL AREA FOR FLAT ROOF.
  
 2- FLAT ROOF PRODUCT APPROVAL SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA
 07-0730.03 SUBMITTED IS GOING TO BE INSTALLED.
  
 B) CLEARLY IDENTIFY WHICH BASE SHEET FASTENING OPTION
 ON SELECTED ASSEMBLY IS GOING TO BE INSTALLED.
  
 C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. SEE LAST PAGE OF NOA SUBMITTED.
 NOTE: IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT MAY NOT BE USED IN THIS
 BUILDING.
 WHEN DOING THE RAS 117 CALCULATIONS TAKE INTO
 CONSIDERATION THAT ACCORDING THE 2009 REVISIONS TO THE
 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED
 ON EXPOSURE "C".
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712