Plan Review Notes For Permit 09080075 |
Permit Number |
09080075 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-08-05 16:55:49 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PERMIT APPLICATION DESCRIBES "MODIFIED BITUMEN ROOF | | SYSTEM OVER WOOD DECK" ONLY. KEY PLAN SUBMITTED SHOWS | | THE MAIN ROOF AS PITCHED ROOF. ALSO, THERE IS A PRODUCT | | APPROVAL SUBMITTED FOR SHINGLES. CLARIFY SCOPE OF WORK. | | SPECIFY ROOF PITCH FOR SHINGLES. SPECIFY TOTAL AREA FOR | | SHINGLES AND TOTAL AREA FOR FLAT ROOF. | | | | 2- FLAT ROOF PRODUCT APPROVAL SUBMITTED: | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA | | 07-0730.03 SUBMITTED IS GOING TO BE INSTALLED. | | | | B) CLEARLY IDENTIFY WHICH BASE SHEET FASTENING OPTION | | ON SELECTED ASSEMBLY IS GOING TO BE INSTALLED. | | | | C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7. SEE LAST PAGE OF NOA SUBMITTED. | | NOTE: IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #9, THEN IT MAY NOT BE USED IN THIS | | BUILDING. | | WHEN DOING THE RAS 117 CALCULATIONS TAKE INTO | | CONSIDERATION THAT ACCORDING THE 2009 REVISIONS TO THE | | 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED | | ON EXPOSURE "C". | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|