2009-08-17 11:46:57*****FIRE-STAMPED W/PROVISO
  
  
 PLAN SHEETS FP-1 AND FP-2 WERE FIRE-STAMPED ACCORDINGLY
 WITH ATTACHED PROVISO FROM BOTH FIRE AND ENGINEERING;
 READY FOR PERMIT ISSUANCE.
2009-08-05 15:13:59313 CLEMATIS STREET
 INSTALL NEW FIRE SPRINKLER SYSTEM IN EXISTING BUILDING
  
 1. THE FIRE DEPARTMENT CONNECTION (FDC) SHALL BE
 EQUIPPED WITH KNOX LOCKING CAPS TO PREVENT VANDALISM OR
 THEFT.
  
 2. A CHAIN AND LOCK IS REQUIRED ON THE BACKFLOW DEVICE.
  
 3. THE ENTIRE BUILDING IS REQUIRED TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THE INSTALLATION IS TO COMPLY
 WITH NFPA 13, THE STANDARD FOR THE INSTALLATION OF
 AUTOMATIC FIRE SPRINKLERS.
  
 4. A SPARE SPRINKLER BOX, SPARE SPRINKLERS, AND WRENCH
 IS TO BE PROVIDED.
  
 5. A GUAGE IS TO BE PROVIDED ON THE RISER.
  
 6. THE ENTIRE FIRE SPRINKLER SYSTEM IS TO BE PRESSURE
 TESTED AT 200 PSIG FOR A MINIMUM OF AT LEAST TWO HOURS.
  
 7. THE FIRE DEPARTMENT CONNECTION IS TO BE WITHIN 150
 FEET OF A FIRE HYDRANT.
  
 8. A FLOW TEST IS TO BE SCHEDULED AS SOON AS SOON
 POSSIBLE TO VERIFY STATIC AND RESIDENTIAL READINGS.
  
 9. PLEASE SUBMIT CUT-SHEETS ON THE QUICK RESPONSE
 SPRINKLER HEADS PLANNED FOR USE.
  
 10. ENSURE THAT HYDRAULIC CALCULATION PLATES AND VALVE
 SIGNS ARE INSTALLED.
  
  
 APPROVED PROVISO
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OFFIRE PREVENTION