Plan Review Notes For Permit 09080027 |
Permit Number |
09080027 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-08-06 08:06:30 | 2007 FBC W/2007 REVISIONS | | NEW POOL/SPA | | | | DENIED BY PLUMBING | | | | 1) SHOW COMPLIANCE WITH R4101.6.3 WATER VELOCITY. POOL | | PIPING SHALL BE DESIGNED SO THE WATER VELOCITY WILL NOT | | EXCEED 10 FEET PER SECOND (3048 MM/S) FOR PRESSURE | | PIPING AND 8 FEET PER SECOND (2438 MM/S) FOR SUCTION | | PIPING, EXCEPT THAT THE WATER VELOCITY SHALL NOT EXCEED | | 8 FEET PER SECOND (2438 MM/S) IN COPPER TUBING. MAIN | | SUCTION OUTLET VELOCITY MUST COMPLY WITH ANSI/APSP 7. | | SUBMIT CALCULATIONS FOR MAXIMUM SYSTEM FLOW RATE. SEE | | ANSI/APSP-7 2006 SECTIONS 4.4 AND 4.4.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|