Plan Review Notes
Plan Review Notes For Permit 09080027
Permit Number 09080027
Review Stop P
Sequence Number 1
Notes
Date Text
2009-08-06 08:06:302007 FBC W/2007 REVISIONS
 NEW POOL/SPA
  
 DENIED BY PLUMBING
  
 1) SHOW COMPLIANCE WITH R4101.6.3 WATER VELOCITY. POOL
 PIPING SHALL BE DESIGNED SO THE WATER VELOCITY WILL NOT
 EXCEED 10 FEET PER SECOND (3048 MM/S) FOR PRESSURE
 PIPING AND 8 FEET PER SECOND (2438 MM/S) FOR SUCTION
 PIPING, EXCEPT THAT THE WATER VELOCITY SHALL NOT EXCEED
 8 FEET PER SECOND (2438 MM/S) IN COPPER TUBING. MAIN
 SUCTION OUTLET VELOCITY MUST COMPLY WITH ANSI/APSP 7.
 SUBMIT CALCULATIONS FOR MAXIMUM SYSTEM FLOW RATE. SEE
 ANSI/APSP-7 2006 SECTIONS 4.4 AND 4.4.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]