Plan Review Notes
Plan Review Notes For Permit 09070777
Permit Number 09070777
Review Stop M
Sequence Number 1
Notes
Date Text
2009-08-05 19:40:33PASSED WITH THE FOLLOWING CONDITIONS:
  
 1. PROVIDE PRODUCT APPROVALS FOR BUILDING PLAN REVIEW
 PER FAC-RULE 9B-72. PAGE M-2 SHOWS TWO NEW WALL
 LOUVERS.
  
 2. PROVIDE TEST AND BALANCE REPORT AT TIME OF FINAL
 INSPECTION TO VERIFY VENTILATION AIRFLOW RATES IN
 ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2.
  
 3. HP-1 REQUIRES A DUCT MOUNTED SMOKE DETECTOR
 INSTALLED AND CONNECTED TO BUILDING FIRE ALARM SYSTEM
 IN ACCORDANCE WITH FBC-M 606.2.1 AND 606.4.
  
 4. ENERGY CALCULATIONS NOT REVIEWED AS PART OF THIS
 PERMIT FOR COMPLIANCE WITH THE MECHANICAL PROVIDIONS OF
 THE FLORIDA ENERGY CODE. COOLING LOAD CALCULATIONS HAVE
 BEEN DETATCHED FROM ENERGY CALCULATIONS AND RETAINED AS
 PART OF THIS PERMIT RECORD DUE TO INCREASED COOLING
 LOADS ASSOCIATED WITH ADDED OUTSIDE AIR.
  