Plan Review Notes For Permit 09070777 |
Permit Number |
09070777 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-08-05 19:40:33 | PASSED WITH THE FOLLOWING CONDITIONS: | | | | 1. PROVIDE PRODUCT APPROVALS FOR BUILDING PLAN REVIEW | | PER FAC-RULE 9B-72. PAGE M-2 SHOWS TWO NEW WALL | | LOUVERS. | | | | 2. PROVIDE TEST AND BALANCE REPORT AT TIME OF FINAL | | INSPECTION TO VERIFY VENTILATION AIRFLOW RATES IN | | ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2. | | | | 3. HP-1 REQUIRES A DUCT MOUNTED SMOKE DETECTOR | | INSTALLED AND CONNECTED TO BUILDING FIRE ALARM SYSTEM | | IN ACCORDANCE WITH FBC-M 606.2.1 AND 606.4. | | | | 4. ENERGY CALCULATIONS NOT REVIEWED AS PART OF THIS | | PERMIT FOR COMPLIANCE WITH THE MECHANICAL PROVIDIONS OF | | THE FLORIDA ENERGY CODE. COOLING LOAD CALCULATIONS HAVE | | BEEN DETATCHED FROM ENERGY CALCULATIONS AND RETAINED AS | | PART OF THIS PERMIT RECORD DUE TO INCREASED COOLING | | LOADS ASSOCIATED WITH ADDED OUTSIDE AIR. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|