2009-07-31 19:27:20 | ** DENIED REVIEW ** |
| |
| ** PLANS ARE COMING BACK FOR COMMENTS WITH RESPECT TO |
| UNITY OF TITLE. |
| |
| |
| |
| 1) NOTE: PANEL SCHEDULE WILL BE REQUIRED TO BE REVISED |
| TO ALL ROOMS/AREAS AND LOCATIONS TO BE SPECIFIC. ** THE |
| USE OF GENERAL LIGHTING* MAY NOT BE USED. |
| SEE UPDATED 408.4 OF THE 2005 NEC. |
| ** PLANS INDICATES CIRCUIT SUCH AS WASHER #9 ON PANEL |
| SCHEDULE T15 TO REMAIN * AS IS* HOWEVER THE PLANS MAKE |
| NOTES TO REMOVE BOTH THE WASHER AND DRYER CIRCUITS? |
| ** PLANS INDICATES CIRCUIT T15 -28 AS A LIGHTING |
| CIRCUIT YET THE T15 PANEL SCHEDULE INDICATES THIS AS A |
| WATER FOUNTAIN DEDICATED CIRCUIT? IT APPEARS 26 AND 28 |
| ARE SWITCHED. |
| ** SEE BATH ROOMS T15, 11, 13, 21, FIRST FLOOR, SECOND |
| FLOOR. |
| |
| 2) NOTE: PLEASE INDICATE ALLOWANCE/LIGHTING FOR J-BOX |
| IN CORRIDOR 105 DIRECTLY IN FRONT OF T15 PANEL. |
| PLEASE KNOW THAT THE SPECIFIC FIXTURES WHICH ARE NOW |
| SHOWN AS A 200WATT ALLOWANCE WILL BE REQUIRED TO BE |
| SHOWN ON FIXTURE LEGEND BEFORE THE END OF PROJECT. |
| KITCHEN AREA IS NOT FOOD SERVICE DESIGNATION AS WOULD |
| BE IN RESTAURANT OCCUPANCY. THIS WILL NOT AFFECT |
| CALCULATIONS. |
| |
| 3) NOTE: PLEASE SHOW THE REQUIRED SIGN CIRCUIT PER |
| 600.5 AND ADD LOADS ACCORDINGLY. |
| |
| 4) NOTE: PLEASE INDICATE NORMAL AND EMERGENCY EGRESS |
| LIGHTING LEVELS FOR STAIRS PER NFPA-101 7.8.1.3, |
| 7.9.2.1, .2.2. |
| FBC 1006.1 |
| |
| ** PER BUILDING OFFICIAL, REJECTED PLANS/PERMIT |
| APPLICATION ARE NO LONGER GIVEN BACK TO CONTRACTOR. |
| |
| ** PLEASE ALSO BE AWARE THE WEEK STARTING AUGUST 17TH, |
| THE CONSTRUCTION SERVICES DEPARTMENT WILL BE CLOSING ON |
| FRIDAY OF EACH WEEK UNTIL FURTHER NOTICE. THE 21ST OF |
| AUGUST WILL BE THE FIRST FRIDAY OF CLOSING. THERE WILL |
| NO LONGER BE THE ROTATING SCHEDULE CURRENTLY IN EFFECT. |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |