Plan Review Notes
Plan Review Notes For Permit 09070582
Permit Number 09070582
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-23 17:22:56RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C", NOT "B". SEE 2009 REVISIONS SEC. R301.2.4.3 .
 ENGINEER NEEDS TO PROVIDE CALCULATIONS FOR BUILDING
 LOCATED ON EXPOSURE "C".
  
 2- ENGINEER TO PROVIDE RAS 117 CALCULATIONS FOR
 INSULATION FASTENING AS REQUIRED BY GENERAL LIMITATION
 #7 ON SHEET 7 OF NOA 07-0710.02 SUBMITTED. INFORMATION
 SUBMITTED HAS NOTHING TO DO WITH THE RAS 117
 CALCULATIONS. SEE RAS 117 CALCULATIONS AND PROVIDE
 REQUIRED INFORMATION.
  
 3- ACCORDING TO SEC. 8.1 OF RAS 117 CALCULATIONS THE
 MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN 4
 IN. O.C. ENGINEER IS SPECIFYING FASTENERS AT 3" O.C. IN
 ZONE #3. SEE RAS 117 CALCULATIONS AND REVISE AS
 REQUIRED. ALSO, ENGINEER TO SEE FIGURE 1 THRU FIGURE 4
 FOR PROPER LOCATION OF INSULATION FASTENERS.
  
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 5- OWES $104.59. THERE WAS A MISTAKE ON THE PERMIT FEES
 AT TIME OF PERMIT APPLICATION.
  