Plan Review Notes
Plan Review Notes For Permit 09070567
Permit Number 09070567
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-17 08:59:59 
 ** DENIED REVIEW **
  
 1) NOTE: PLANS HAVE NOT BEEN SUBMITTED UNDER LICENSED
 CONTRACTOR FOR PERMIT APPLICATION.
 PERMIT APPLICATION MAY NOT BE ISSUED UNTIL A LICENSED
 CONTRACTOR HAS APPLIED AND FILLED OUT PERMIT
 APPLICATION.
  
 2) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL
 SERVICE EQUIPMENT INCLUDING MAIN. 110.9
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.AB.5, 13-415.B.2.2
  
 4) NOTE: PLANS HAS NOTES WHICH MENTIONS AMENDMENTS AS
 OF 6/01/09 HOWEVER THERE ARE NO KNOWN AMENDMENTS
 ADOPTED BY THE STATE ON THIS DATE.
 ALL PERMIT APPLICATIONS MADE AFTER MARCH 1ST, 2009
 PLACES ALL MINIMUM DESIGNS UNDER 2007 FBC W/ 2009
 SUPPLEMENTS. THE EDITION OF THE NEC/ NFPA-70 AS OF THIS
 MARCH DATE IS THE 2005.
 ** PLEASE EXPLAIN THE DATE NOTED.
  
 5) NOTE: PLEASE BE SURE TO INDICATE THE TYPE OF TIME
 CLOCK MEETING 13-415.AB.1.4. THE TIME CLOCK MUST BE
 ASTRONOMICAL WITH A MINIMUM OF 10HR BACK UP FOR
 PROGRAMMING.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  