Plan Review Notes
Plan Review Notes For Permit 09070491
Permit Number 09070491
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-22 11:00:21RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- PROPOSED SCOPE OF WORK IS FOR MORE THAN 25% OF THE
 ROOF. NEED TO RE-ROOF ENTIRE ROOF AS REQUIRED BY SEC.
 611.1.1 OF 2007 FLORIDA EXISTING BUILDING CODE.
 IN ADDITION ENGINEER REPORT SUBMITTED STATES ALSO THAT
 ENTIRE ROOF NEEDS TO BE REPLACED BECAUSE ROOF DOESN'T
 MEET THE FBC REQUIREMENTS.
  
 3- REVISE PERMIT APPLICATION TO RE-ROOF ENTIRE ROOF,
 NOT REPAIRS AND REVISE VALUATION AS REQUIRED. SPECIFY
 TOTAL SQUARE FOOTAGE, ROOF PITCH AND MEAN ROOF HEIGHT.
 PERMIT FEES WILL BE ADJUST ACCORDINGLY.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVAL AS REQUIRED BY
 DCA RULE 9B-72 FOR THE ROOF TILE TO BE INSTALLED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712