2009-07-21 15:50:40 | RESIDENTIAL (R3) REROOF. BUILDING REVIEW CHECKLIST. |
| 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| |
| 2- IF BUILDING IS INSURED FOR $300.000 OR MORE, THEN |
| NEED TO COMPLY WITH THE ROOF MITIGATION SEC. 611.8 OF |
| 2009 REVISIONS TO THE 2007 FLORIDA EXISTING BUILDING |
| CODE. ACCORDING TO THE PROPERTY APPRAISAL THE STRUCTURE |
| IS WORTH MORE THAN $300.000. PROVIDE COMPLETE |
| INFORMATION SHOWING COMPLIANCE WITH THE ROOF TO WALL |
| CONNECTIONS. THIS IS DONE UNDER A SEPARATE PERMIT AND |
| IT CAN'T BE DONE BY THE ROOFING CONTRACTOR UNLESS |
| ROOFING CONTRACTOR HOLDS A GENERAL, BUILDING OR |
| RESIDENTIAL CONTRACTOR LICENSE. THIS NEEDS TO BE DONE |
| UNDER A SEPARATE PERMIT. |
| |
| 3- FLAT ROOF COMMENTS: |
| A) ACCORDING TO THE MIAMI-DADE WEBSITE, NOA 07-1203.01 |
| SUBMITTED FOR FLAT ROOF IS SUPERSEDED. NEED TO PROVIDE |
| CURRENT NOA. |
| |
| B) CLEARLY MARK WHICH FLAT ROOF BASE SHEET FASTENING |
| OPTION IS GOING TO BE INSTALLED. |
| |
| C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| PERIMETER AND CORNER AS REQUIRED BY GENERAL LIMITATION |
| #7. SUCH CALCULATIONS NEED TO BE SIGNED AND SEALED BY |
| ANY OF THE DESIGN PROFESSIONALS LISTED ON THE GENERAL |
| LIMITATION. SEE GENERAL LIMITATION #7 ON LAST PAGE OF |
| NOA SUBMITTED. |
| NOTE: DESIGN PROFESSIONAL TO TAKE INTO CONSIDERATION |
| THAT THIS BUILDING IS LOCATED ON EXPOSURE "C" WHEN |
| DOING THE CALCULATIONS. |
| |
| 4- ACCORDING TO COPY OF CONTRACT SUBMITTED THERE ARE |
| TWO NEW SKYLIGHTS TO BE INSTALLED. NEW SKYLIGHTS IS OUT |
| OF THE SCOPE OF WORK OF THE ROOFING CONTRACTOR UNLESS |
| ROOFING CONTRACTOR HOLDS PROPER LICENSE TO PERFORM SUCH |
| WORK. THIS NEEDS TO BE DONE UNDER SEPARATE PERMIT. |
| |
| 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR THE SKYLIGHTS TO BE INSTALLED. |
| |
| 6- PROVIDE 2 COPIES OF ROOF TILE PRODUCT APPROVALS. |
| ONLY ONE WAS SUBMITTED. |
| |
| 7- SHOW ON ROOF TILE PRODUCT APPROVAL HOW IS THE TILE |
| GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| TILE ATTACHMENT RESISTANCE AND DESIGN PRESSURES AS |
| REQUIRED BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. |
| IF ADHESIVE IS USED, THEN PROVIDE 2 COPIES OF PRODUCT |
| APPROVAL. SEE ROOF TILE NOA FOR LISTED TYPE OF |
| ADHESIVES TO BE USED. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |