2009-10-19 09:21:14 | BUILDING PLAN REVIEW |
| PERMIT: 09070394 |
| ADD: 800 HANDY AVE |
| CONT: TO BE DETERMINED/ DEAN MOSLEY |
| TEL: (772)626-6316 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| OCT 19/2009 |
| |
| 1-3 COMPLIED. |
| |
| 4) TRUSS PACKAGE: |
| 4A) COMPLIED. |
| |
| 4B) ONLY SHINGLES CAN BE APPLIED TO THIS ROOF, WITH A |
| 7.0 DEAD LOAD THERE IS NO ALLOWANCE FOR A SECOND LAYER |
| OF SHINGLES WITHOUT THE REMOVAL OF THE FIRST LAYER OR |
| ROOF TILE. |
| |
| 5) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| MISSILE TEST. |
| |
| 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIESOF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: |
| 9B-72.010(31) |
| 6A) SINGLE HUNG WINDOWS (B) |
| |
| 6B) MULLIONS (B) |
| |
| 6C) EXTERIOR SWING DOORS (A) |
| |
| 6D) LOUVERS (SOFFITS) (C) |
| |
| 6E) SHUTTERS (E) IF LARGE MISSILE IMPACT WINDOWS ARE |
| NOT INSTALLED |
| |
| 6F) ROOFING ASSEMBLIES: SHINGLES |
| |
| 7) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 8) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 9) SHEET T-1 INDICATES THE CALCULATIONS FOR EAVE |
| VENTING BUT NO PROVISIONS ARE PROVIDED FOR THE REQUIRED |
| 50% OF THE UPPER AIR VENTILATION CLOSER TO THE RIDGE. |
| R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING |
| AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE |
| SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL |
| AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50 |
| PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED |
| VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN |
| THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT |
| LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS |
| WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED |
| BY EAVE OR CORNICE VENTS. |
| |
| R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING |
| AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE |
| SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL |
| AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50 |
| PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED |
| VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN |
| THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT |
| LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS |
| WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED |
| BY EAVE OR CORNICE VENTS. |
| |
| 10) CONTRACTOR TO BE SIGNED ON BEFORE THE PERMIT CAN BE |
| ISSUED. FL S S 489. |
| |
| SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR |
| TIMES THE FEE. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| SURVEY: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |