Plan Review Notes
Plan Review Notes For Permit 09070394
Permit Number 09070394
Review Stop B
Sequence Number 2
Notes
Date Text
2009-10-19 09:21:14BUILDING PLAN REVIEW
 PERMIT: 09070394
 ADD: 800 HANDY AVE
 CONT: TO BE DETERMINED/ DEAN MOSLEY
 TEL: (772)626-6316
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 OCT 19/2009
  
 1-3 COMPLIED.
  
 4) TRUSS PACKAGE:
 4A) COMPLIED.
  
 4B) ONLY SHINGLES CAN BE APPLIED TO THIS ROOF, WITH A
 7.0 DEAD LOAD THERE IS NO ALLOWANCE FOR A SECOND LAYER
 OF SHINGLES WITHOUT THE REMOVAL OF THE FIRST LAYER OR
 ROOF TILE.
  
 5) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIESOF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 9B-72.010(31)
 6A) SINGLE HUNG WINDOWS (B)
  
 6B) MULLIONS (B)
  
 6C) EXTERIOR SWING DOORS (A)
  
 6D) LOUVERS (SOFFITS) (C)
  
 6E) SHUTTERS (E) IF LARGE MISSILE IMPACT WINDOWS ARE
 NOT INSTALLED
  
 6F) ROOFING ASSEMBLIES: SHINGLES
  
 7) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) SHEET T-1 INDICATES THE CALCULATIONS FOR EAVE
 VENTING BUT NO PROVISIONS ARE PROVIDED FOR THE REQUIRED
 50% OF THE UPPER AIR VENTILATION CLOSER TO THE RIDGE.
 R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING
 AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE
 SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL
 AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50
 PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED
 VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN
 THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT
 LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS
 WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED
 BY EAVE OR CORNICE VENTS.
  
 R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING
 AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE
 SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL
 AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50
 PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED
 VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN
 THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT
 LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS
 WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED
 BY EAVE OR CORNICE VENTS.
  
 10) CONTRACTOR TO BE SIGNED ON BEFORE THE PERMIT CAN BE
 ISSUED. FL S S 489.
  
 SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved