2009-07-31 11:21:38 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | ALL COMMENTS RELATE TO SHEET 1 OF 1, UNLESS OTHERWISE | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | OTHERWISE NOTED. | | | | 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN | | IS NEW OR EXISTING. IF NEW PROVIDE AN AIC RATING. SEE | | 230.70(A)(1) FOR DISCONNECT REQUIREMENTS. | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, | | 106.3.5.4 FBC AS AMENDED. | | | | 3} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). | | | | 4} PER 210.52(E) A RECEPTACLE IS REQUIRED AT THE FRONT | | AND BACK OF THE HOUSE (OUTSIDE). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | | | |
|