Plan Review Notes
Plan Review Notes For Permit 09070394
Permit Number 09070394
Review Stop B
Sequence Number 1
Notes
Date Text
2009-08-05 12:32:16BUILDING PLAN REVIEW
 PERMIT: 09070394
 ADD: 800 HANDY AVE
 CONT: TO BE DETERMINED/ DEAN MOSLEY
 TEL: (772)626-6316
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 AUGUST 05/2009
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) SHEET A1 INDICATES VARIOUS DOCUMENTS AFFIDAVITS FROM
 PALM BEACH COUNTY BUILDING DEPARTMENT, THESE DOCUMENTS
 ARE NOT IN ACCEPTED IN THE CITY OF WEST PALM BEACH, WE
 ARE OUR OWN AHJ AUTHORITY HAVING JURISDICTION( HOME
 RULE). PLEASE CORRECT.
  
 3) SHEET# 1 UNDER SCOPE OF WORK LIST THIS PROJECT AS A
 REPAIR AND ONLY SUBJECT TO CHAPTER 5 & 6 OF THE FL
 EXISTING BUILDING CODE 2007 W/ 2009 SUPPLEMENTS. PLEASE
 REVIEW AND REVISE IN ACCORDANCE WITH ;
 3A) DEFINITION OF REPAIR IS; THE PATCHING, RESTORATION
 AND/OR MINOR REPLACEMENT OF MATERIALS, ELEMENTS,
 COMPONENTS, EQUIPMENT AND/OR FIXTURES FOR THE PURPOSES
 OF MAINTAINING SUCH MATERIALS, ELEMENTS, COMPONENTS,
 EQUIPMENT AND/OR FIXTURES IN GOOD OR SOUND CONDITION.
  
 3B) DEFINITION OF LEVEL III;
 405.1 SCOPE. LEVEL 3 ALTERATIONS APPLY WHERE THE WORK
 AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF THE
 BUILDING AND MADE WITHIN ANY 12-MONTH PERIOD.
  
 EXCEPTION: WORK AREAS IN WHICH THE ALTERATION WORK IS
 EXCLUSIVELY PLUMBING, MECHANICAL OR ELECTRICAL SHALL
 NOT BE INCLUDED IN THE COMPUTATION OF TOTAL AREA OF ALL
 WORK AREAS.
  
 3C) 405.2 APPLICATION. LEVEL 3 ALTERATIONS SHALL COMPLY
 WITH THE PROVISIONS OF CHAPTERS 6 AND 7 FOR LEVEL 1 AND
 2 ALTERATIONS, RESPECTIVELY, AS WELL AS THE PROVISIONS
 OF CHAPTER 8.
 BY THE DEFINITONS THIS IS DETERMINED TO BE A LEVEL
 THREE ALTERATION. THE DESIGNER OF RECORD MUST COMPLETE
 A STRUCTURAL EVALUATION IN COMPLIANCE WITH 807.5.1.
 807.5.1 EVALUATION AND ANALYSIS. AN ENGINEERING
 EVALUATION AND ANALYSIS THAT ESTABLISHES THE STRUCTURAL
 ADEQUACY OF THE ALTERED STRUCTURE SHALL BE PREPARED BY
 A REGISTERED ARCHITECT OR ENGINEER AND SUBMITTED TO THE
 BUILDING CODE OFFICIAL. DOES THIS TRUCTURE HAVE COLUMNS
 THAT WILL MAKE A CONTINIOUS LOAD PATH TO THE
 FOUNDATION?
  
 3D) 807.5.2 SUBSTANTIAL STRUCTURAL ALTERATION. WHERE
 MORE THAN 30 PERCENT OF THE TOTAL SUM OF FLOOR AND ROOF
 AREAS OF THE BUILDING OR STRUCTURE HAS BEEN OR IS
 PROPOSED TO BE INVOLVED IN STRUCTURAL ALTERATION WITHIN
 A 12-MONTH PERIOD, THE EVALUATION AND ANALYSIS SHALL
 DEMONSTRATE THAT THE ALTERED BUILDING OR STRUCTURE
 COMPLIES WITH THE FLORIDA BUILDING CODE, BUILDING FOR
 WIND LOADING.
  
 4) TRUSS PACKAGE:
 4A) BOTTOM CHORD LIVE LOAD, AS INDICATED WITHIN THE
 TRUSS ENGINEERING THE BOTTOM CHORD LIVE LOAD AS ZERO
 LBS. PLEASE REVIEW TABLE 301.5 LIVE LOADS FOOTNOTE "B"
 ATTICS WITHOUT STORAGE MUST MEET ANY OF THE FOLLOWING
 CRITERIA, THESE TRUSSES DO NOT MEET ANY OF THE CRITERIA
 REQUIRING 20 LBS LIVE LOAD ON THE BOTTOM CHORD. TABLE
 R301.5.FOOTNOTE (B). ATTICS WITHOUT STORAGE ARE THOSE
 WHERE THE MAXIMUM CLEAR HEIGHT BETWEEN JOIST AND RAFTER
 IS LESS THAN 42 INCHES, OR WHERE THERE ARE NOT TWO OR
 MORE ADJACENT TRUSSES WITH THE SAME WEB CONFIGURATION
 CAPABLE OF CONTAINING A RECTANGLE 42 INCHES HIGH BY 2
 FEET WIDE, OR GREATER, LOCATED WITHIN THE PLANE OF THE
 TRUSS. FOR ATTICS WITHOUT STORAGE, THIS LIVE LOAD NEED
 NOT BE ASSUMED TO ACT CONCURRENTLY WITH ANY OTHER LIVE
 LOAD REQUIREMENTS.
  
 4B) NOTE THIS WILL BE A BUILDING STIPULATION NOTED ON
 THE PERMIT AND CERTIFICATE OF OCCUPANCY,BUILDING
 PROVISO: THAT ONLY SHINGLES CAN BE APPLIED TO THIS
 ROOF, WITH A 7.0 DEAD LOAD THERE IS NO ALLOWANCE FOR A
 SECOND LAYER OF SHINGLES WITHOUT THE REMOVAL OF THE
 FIRST LAYER OR ROOF TILE.
  
 5) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIESOF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 9B-72.010(31)
 6A) SINGLE HUNG WINDOWS (B)
  
 6B) MULLIONS (B)
  
 6C) EXTERIOR SWING DOORS (A)
  
 6D) LOUVERS (SOFFITS) (C)
  
 6E) SHUTTERS (E) IF LARGE MISSILE IMPACT WINDOWS ARE
 NOT INSTALLED
  
 6F) ROOFING ASSEMBLIES: SHINGLES
  
 7) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) SHEET T-1 INDICATES THE CALCULATIONS FOR EAVE
 VENTING BUT NO PROVISIONS ARE PROVIDED FOR THE REQUIRED
 50% OF THE UPPER AIR VENTILATION CLOSER TO THE RIDGE.
 R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING
 AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE
 SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL
 AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50
 PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED
 VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN
 THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT
 LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS
 WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED
 BY EAVE OR CORNICE VENTS.
  
 R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING
 AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE
 SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL
 AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50
 PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED
 VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN
 THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT
 LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS
 WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED
 BY EAVE OR CORNICE VENTS.
  
 10) CONTRACTOR TO BE SIGNED ON BEFORE THE PERMIT CAN BE
 ISSUED. FL S S 489.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  