Plan Review Notes
Plan Review Notes For Permit 09070391
Permit Number 09070391
Review Stop E
Sequence Number 2
Notes
Date Text
2009-09-20 09:36:51** PROVISO/ REVISION REQUIRED **
  
 PLANS ARE REQUIRED TO BE REVISED BEFORE ROUGH
 ELECTRICAL INSPECTION.
  
  
 1) NOTE: ALL EMERGENCY/EXIT LIGHTS SHALL BE CIRCUITED
 TO LOCAL LIGHTING BRANCH CIRCUIT PER 700.12F. AS SHOWN
 ON PLANS, THE CIRCUITING DOES NOT MEET THE EXCEPTION IN
 THE NEC. SHOWN ON A NEW CIRCUIT #5, WHEN THEY ARE
 REQUIRED TO BE SPLIT BETWEEN #6 AND #8.
  
 2) NOTE: AUTOMATED LIGHTING CONTROLS FOR NEW BEING
 INSTALLED IS REQUIRED FOR NEW OFFICE AREA. PLEASE SEE
 13-415.AB.1.1,.1.2. THIS IS A BUILDING BY DEFINITION
 GREATER THAN 5K SQ FT.
  
 3) NOTE: EXTERIOR LIGHTING CONTROL SHALL MEET
 13-415.AB.1.4. PLANS INDICATE A SINGLE POLE SWITCH
 WHICH IS NOT PERMITTED. THE CODE REQUIRES ONE OF THE
 METHODS NOTED IN SECTION GIVEN. THIS HAS NOTHING TO DO
 WHETHER OR NOT THE BUILDING IS GREATER THAN 5K SQ FT.
  
 4) NOTE: PLEASE ACCURATELY SHOW THE ENTIRE ELECTRICAL
 SERVICE OF THE BUILDING. SERVICE AS SHOWN IS NOT
 ACCURATE FOR ENTIRE SERVICE ON BUILDING.
  
 5) NOTE: FIXTURES ON PLANS NEED TO BE SPECIFIC IN ORDER
 TO VERIFY 13-415.AB.5. STATING A 2X4 FIXTURE COULD MEAN
 THE FIXTURE COULD BE 30VA,32VA, 56VA, 58VA, 60VA, 64VA
 OR MORE. THE LPD SHOWN ON PLANS CAN NOT BE CONFIRMED AS
 MEETING THE MAXIMUM ALLOWANCES.
  
  
 ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT
 INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS
 REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  