2009-07-29 14:20:55REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PREVIOUSLY UNCONDITIONED EXISTING BUILDINGS WHICH
 WERE PERMITTED PRIOR TO MARCH 15, 1979 TO WHICH HEATING
 OR COOLING SYSTEMS ARE ADDED SHALL MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B OF
 SUBCHAPTER 13-4 FOR COMMERCIAL APPLICATIONS AND METHOD
 B OF SUBCHAPTER 13-6 FOR RESIDENTIAL APPLICATIONS OF
 THE CODE FOR INSULATION, HVAC SYSTEMS AND EXTERIOR
 ENVELOPE FOR THOSE COMPONENTS WHICH ARE BEING
 RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B
 SECTION 13-101.4.1.1.
  
 2. PROVIDE COOLING LOAD CALCULATIONS ATTACHED TO THE
 METHOD B ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH
 FBC-B SECTION 13-407.AB.1.
  
 3. PROVIDE ENSTALLATION DETAIL FOR INSTALLATION OF
 CONDENSING UNITS ON THE ROOF IN ACCORDANCE WITH FBC-M
 301.12 AND FBC-B 1509.7.
  
 4. APPLIANCES ON ROOFS OR ELEVATED STRUCTURES SHALL
 COMPLY WITH THE REQUIREMENTS OF FBC-M 304.10 FOR GUARDS
 AND FBC-M 306.5 FOR ACCESS.
  
 5. PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS IN
 ACCORDANCE WITH FBC-M 303.1
  
 6. A RECEPTACLE OUTLET SHALL BE PROVIDED AT OR NEAR THE
 ROOFTOP EQUIPMENT LOCATION IN ACCORDANCE WITH FBC-M
 306.5.2.
  
 7. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-M 307.2.1.
  
 8. SHOW TEMINATION LOCATION OF BATHROOM EXHAUST IN
 ACCORDANCE WITH FBC-M 401.4 AND FBC-M 501.2.
  