Notes |
Date |
Text |
2009-07-29 16:23:38 | | | PROVISO | | | | THE PLANS ARE INCOMPLETE. PLEASE RESUBMIT A REVISION | | SHOWING ACTUAL CONDITIONS PRIOR TO CALLING ROUGH | | ELECTRICAL INSPECTION. THE REVIEWED PLAN MUST BE ON THE | | JOB SITE AT TIME OF INSPECTION. ALLOW AT LEAST ONE WEEK | | (PER TRADE) FOR PLAN REVIEW. | | | | 1} THE EM LIGHTS MUST BE SHOWN WIRED TO THE LOCAL | | BRANCH CIRCUIT, 700.12(F)(4). | | | | 2} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14, RECEPTACLE PER 210.63. | | | | 3} A RECEPTACLE PER 210.63 IS REQUIRED ON THE ROOF. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|