Plan Review Notes For Permit 09070384 |
Permit Number |
09070384 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-09-16 16:37:25 | RESUBMITTED PLANS WERE HELD AT EXPEDITER'S REQUEST TO | | ALLOW TIME TO PROVIDE MISSING INFORMATION. TO THIS | | DATE, REQUESTED INFORMATION WAS NOT PROVIDED AND | | PREVIOUS REVIEW COMMENTS REMAIN UNADDRESSED. | | | | 1. PROVIDE SITE PLAN SHOWING LOCATION OF EXHAUST FAN | | AND MAKEUP AIR INTAKE TO DEMONSTRATE COMPLIANCE WITH | | FBC-M 401.4.1, FBC-M 506.3.12 AND FBC-M 508.1. | | NOTE: IT APPEARS LIKELY THAT A SIDEWALL MAKEUP AIR | | INTAKE WILL BE WITHIN 10' OF DRIVEWAY IN VIOLATION OF | | FBC-M 401.4.1. | | | | 2. PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE | | CAPABILITIES OF EXHAUST FAN IN ACCORDANCE WITH FBC-M | | 301.12. | | | | 3. PLAN SHOWS LOUVER AT MAKEUP AIR INTAKE. PROVIDE | | PRODUCT APPROVAL FOR PROPOSED LOUVER IN ACCORDANCE WITH | | FAC RULE 9B-72. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|