Plan Review Notes
Plan Review Notes For Permit 09070384
Permit Number 09070384
Review Stop M
Sequence Number 1
Notes
Date Text
2009-08-14 14:55:101. PROVIDE SITE PLAN SHOWING LOCATION OF EXHAUST FAN
 AND MAKEUP AIR INTAKE TO DEMONSTRATE COMPLIANCE WITH
 FBC-M 401.4.1, FBC-M 506.3.12 AND FBC-M 508.1.
 NOTE: IT APPEARS LIKELY THAT A SIDEWALL MAKEUP AIR
 INTAKE WILL BE WITHIN 10' OF DRIVEWAY IN VIOLATION OF
 FBC-M 401.4.1.
  
 2. PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE
 CAPABILITIES OF EXHAUST FAN IN ACCORDANCE WITH FBC-M
 301.12.
  
 3. PLAN SHOWS LOUVER AT MAKEUP AIR INTAKE. PROVIDE
 PRODUCT APPROVAL FOR PROPOSED LOUVER IN ACCORDANCE WITH
 FAC RULE 9B-72.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved