Date |
Text |
2009-08-05 16:37:06 | DENIED |
| REFERENCE: |
| FBC-2007 W/2009 SUPPLEMENTS |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 11 |
| |
| 1. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. |
| INDICATE LOCATION ON THE FLOOR PLAN. |
| |
| 2. SHT P-1 TITLE BLOCK INDICATES SUITE 104-B WHERE AS |
| THE APPLICATION AND SYSTEM INDICATE THE SUITE NUMBER AS |
| 205. ALSO THE FLOOR PLAN DOES NOT REFLECT THE FLOOR |
| PLAN SHOWN ON THE ARCHITECTURAL SHEETS. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 3. SHT A-1 FLOOR PLAN. SHOW THE CLEAR FLOOR SPACE AND |
| TURNING AREA REQUIRED BY SECTIONS 11-4.16.2, 11-4.19.3 |
| & 11-4.22.3. IT APPEARS THAT THE DOOR MAY SWING INTO |
| THE CLEAR FLOOR SPACE OF THE W/C. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |